VFD-C2000 Drive Settings

When you operate VFD-C2000 through CMC-PN01, you should set the
communication card as the source of VFD-C2000 controls and settings. You need to use
the keypad to configure the following parameter addresses to the corresponding values:
Keypad
Parameter No.
Pr.00-20
Pr.00-21
Pr.09-30
Pr.09-60
Note: To make PLC or the host controller identify CMC-PN01, it is necessary to load the
product description file (GSDML). You can download it directly from Delta's official
website.
CMC-PN01 Operation Manual
VFD-C2000 PROFINET Communication Card CMC-PN01
Settings/
Displayed Value
8
Set communication card as the source of frequency command.
5
Set communication card as the source of control.
1
Decoding method is either 60xx or 20xx.
Communication card identification:
12
When CMC-PN01 communication card is connected, the value of
this parameter displays "12".
Description of Function
11