Pre-Installation - Siemens ZIC-4AC Installation Instructions Manual

Zone interface card
Table of Contents

Advertisement

PRE-INSTALLATION

GND FAULT
ZONE 1 (2, 3, 4) ACTIVE
TROUBLE
Three rotary dial switches at the bottom of the front panel are used to set
the CAN network address of the ZIC-4AC.
The following components must be set prior to inserting the card to the CC-5
(refer to Figure 2):
S1: Not used
Switch position has to be off
(upper position)
S2: Not used
All four switch positions have to
be off (left position)
S3: Reset Switch
Momentarily Closed switch that
when pressed will initiate a hard
reset to the ZIC-4AC (similar to a
cold boot).
S5: Input Power Select
This switch selects the source of
voltage input to power the ZIC-
4AC. BP Power indicates that
the input is derived from the
backplane of the CC -2/CC-5 and
EXT Power indicates that the
input is derived from E5/E11
terminal of the CC-2/CC-5,
normally connected to non-
power limited output of the PSC-
12/PSX-12. It is important to take
into account the source of the
voltage during power
calculations.
S4, S6, S7: Network Address Switch
Set the two-digit CAN network address for the ZIC-4AC using the three rotary
dial address switches located near the bottom of the front panel. (Refer to
Figure 1 for the location of the switches.) The address for the ZIC -4AC must
be the same as the address selected for it in the Zeus Programming Tool. To
set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 23, set the pointer for
the HUNDREDS dial to "0", set the pointer for the TENS dial to "2", and set
the pointer for the ONES dial to "3". The range of allowable addresses is
from 001 to 099 (leading zeros must be used).
3
(Yellow)
Normally OFF. When illuminated,
indicates that the ZIC-4AC has
detected either a negative or positive
ground fault on its field wiring.
(Red)
Normally OFF. When illuminated,
indicates that Zone 1 (2, 3, 4) is active.
(Yellow)
Normally OFF. When illuminated,
indicates that the ZIC-4AC has
detected a trouble on Zone 1 (open
circuit or short circuit).
Figure 2
ZIC-4AC Switch and Jumper Location
for Strobe usage
A24205-A334-B827
P/N 315-035850-2