5 Mounting / Installation

5.1 Mounting on U-rail or flat surface

Building Technologies
Fire Safety
The multi line separator module can be installed directly or in an additional
housing. The additional housing FDCH221 must be ordered separately.
See also
2 Housing FDCH221 [➙ 23]
The multi line separator module can be installed directly without additional housing
in the following ways:
Directly on a flat surface with two screws
With two mounting feet vertically on a U-rail TS35
With two mounting feet horizontally on a U-rail TS35
Proceed as follows to mount the multi line separator module:
1. Mount the multi line separator module on a flat surface with 2 screws or with
two mounting feet on a U-rail (see following figures). Pick a suitable position
during mounting to ensure that the LEDs are visible at all times.
2. Connect the cables to the terminals (see 'Installation and connection diagram
[➙ 32]').
3. If using shielded FDnet/C-NET cables, connect cable shielding to connection
terminal DBZ1190-AB. The shielding must not touch any external ground
potentials or metal parts.
4. Secure cables on module carrier with cable ties.
Figure 8: Direct mounting on a flat surface
Mounting / Installation
Mounting on U-rail or flat surface
118 mm
5
Ø max. 4.5 mm
29 | 42
A6V10224006_g_en_--
2018-10-25