Function description
Control unit
(cont.)
The primary store is heated up to the set
DHW temperature. Heating stops when
the specified temperature has been
reached at the cylinder temperature sen-
sor.
Reheating when DHW is drawn off
When DHW is drawn off, cold water
enters at the bottom of the primary
store.
The heating circuit pump is switched ON
and the 3-way diverter valve is changed
over, if the cylinder temperature sensor
recognises a temperature lower than the
set value.
■ The cylinder primary pump is switched
ON if the boiler water temperature ≥
set DHW temperature.
■ The burner is switched ON if the boiler
water temperature ≤ set DHW temper-
ature, and the cylinder primary pump
is switched ON when the required
boiler water temperature is reached.
DHW heating via solar collectors
If a temperature differential is measured
between the collector temperature sen-
sor and the cylinder temperature sensor
of the solar control module, which is
greater than the start temperature differ-
ential set in the control unit, the solar cir-
cuit pump is started and the DHW cylin-
der is heated.
152
After heating has ended, the cylinder pri-
mary pump and the 3-way diverter valve
remain on for a further 30 s.
DHW is regulated to the set temperature
via the outlet temperature sensor.
The primary store continues to be heated
up after the draw off process has termi-
nated, until the set DHW temperature
has been reached at the cylinder tem-
perature sensor.
The cylinder primary pump and the 3-
way diverter valve remain on for a further
30 s.
The pump is stopped if the temperature
falls below the stop temperature differ-
ential between the collector temperature
sensor and the cylinder temperature
sensor of the solar control module.
The solar circuit pump is stopped if the
set maximum temperature or the tem-
perature set at the temperature limiter is
reached.