Viessmann VITODENS 242-F Installation And Service Instructions Manual page 107

3.2 to 26 kw gas condensing/solar storage combi boiler gas council no. 41-819-18; 41-819-19 natural gas and lpg version
Table of Contents

Advertisement

"DHW"
(cont.)
Coding in the delivered condition
57:0
Do not adjust
58:0
Without auxiliary function
for DHW heating
5E:0
Do not adjust
5F:0
Do not adjust
65:...
Do not adjust (Informa-
tion on the type of diverter
valve, specified by the
boiler coding card)
67:40
For solar DHW heating:
Set DHW temperature
40 °C. DHW reheating is
suppressed above the
selected set temperature.
(DHW heating by the boil-
er only if solar energy is
not sufficient).
6C:100
Set speed of internal cir-
culation pump during
DHW heating 100 %
6F:...
Max. heating output for
DHW heating in %, speci-
fied by the boiler coding
card
71:0
DHW circulation pump:
"ON" according to time
program
72:0
DHW circulation pump:
"ON" according to time
program
Possible change
Note
Max. value subject to boiler
coding card.
Observe the max. permis-
sible DHW temperature.
58:10
Input of a second set DHW
to
temperature, adjustable
58:60
from 10 to 60 °C (observe
coding addresses "56" and
"63" in this group)
67:0
Set DHW temperature ad-
to
justable from 0 to 95 °C
67:95
(limited by boiler-specific
parameters).
Observe the setting of cod-
ing address "56".
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
6F:0
Max. heating output for
to
DHW heating adjustable
6F:100
from min. heating output to
100 %
71:1
"OFF" during DHW heating
to set value 1
71:2
"ON" during DHW heating
to set value 1
72:1
"OFF" during DHW heating
to set value 2
72:2
"ON" during DHW heating
to set value 2
Code 2
107

Advertisement