Troubleshooting
Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
E1
Burner in a fault
state
E3
Burner in a fault
state
E4
Burner blocked
E5
Burner blocked
E6
Burner blocked
E7
Burner in a fault
state
132
Cause
Ionisation current
too high during cal-
ibration
Heat transfer too
low during calibra-
tion.
Temperature limit-
er has shut down.
Fault, 24 V supply
voltage
Fault, flame ampli-
fier
System pressure
too low
Ionisation current
too low during cali-
bration
Measures
Check gap between ioni-
sation electrode and burn-
er gauze assembly (see
page 61).
In open flue operation,
prevent high incidence of
dust in the combustion
air.
Press reset button R.
Ensure adequate heat
transfer.
Press reset button R.
Replace control unit.
Replace control unit.
Top up with water.
Check ionisation elec-
trode:
■ Distance to burner
gauze assembly (see
page 61)
■ Contamination of elec-
trode
■ Connecting lead and
plug-in connections
Check flue system; reme-
dy flue gas recirculation if
required.
Press reset button R.