Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Party mode time limit
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h
*1
Start temperature raising
F8:-5
Temperature limit for ter-
minating the reduced
mode -5 ºC, see example
on page 140.
Observe the setting of
coding address "A3"
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 ºC, see
example on page 140.
Increase set flow temperature
FA:20
Raising the set boiler
water temperature or the
set flow temperature
when changing from
operation with reduced
room temperature to
operation with standard
room temperature by
20 %. See example on
page 141.
Duration set flow temperature increase
Fb:30
Duration for raising the
set boiler water tempera-
ture or the set flow tem-
perature (see coding
address "FA") 60 min.
See example on
page 141.
*1
Party mode ends automatically in the "Heating and DHW" program, when the
system changes over to operation with standard room temperature.
(cont.)
Possible change
F2:0
No time limit for party
*1
mode
F2:1
Time limit adjustable from 1
to
to 12 h
*1
F2:12
F8:+10
Temperature limit adjusta-
to
ble from
F8:-60
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Temperature limit for rais-
to
ing the set room tempera-
F9:-60
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50 %
FA:50
Fb:0
Duration adjustable from 0
to
to 300 min;
1 step ≙ 2 min
Fb:150
Code 1