Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
b8
Burner blocked
bA
Mixer regulates to 20
°C flow temperature.
bb
Mixer regulates to 20
°C flow temperature.
bC
Control mode without
remote control
bd
Control mode without
remote control
bE
Control mode without
remote control
bF
Control mode
C1
Control mode
C2
Control mode
C3
Control mode
Cause
Measures
Lead break, flue
Check the flue gas tem-
gas temperature
perature sensor
sensor
Communication
Check the extension kit
error, extension kit
connections and coding
for heating circuit 2
(with mixer)
Communication
Check the extension kit
error, extension kit
connections and coding
for heating circuit 3
(with mixer)
Communication
Check connections, lead,
error, remote con-
coding address "A0" and
trol Vitotrol heating
remote control settings
circuit 1 (without
(see page 143).
mixer)
Communication
Check connections, lead,
error, remote con-
coding address "A0" and
trol Vitotrol heating
remote control settings
circuit 2 (with
(see page 143).
mixer)
Communication
Check connections, lead,
error, remote con-
coding address "A0" and
trol Vitotrol heating
remote control settings
circuit 3 (with
(see page 143).
mixer)
Incorrect LON
Replace the LON commu-
communication
nication module
module
Communication
Check electrical connec-
error extension
tions
EA1
Solar control mod-
Check solar control mod-
ule communication
ule
fault
Extension AM1
Check electrical connec-
communication
tions
error
Troubleshooting
107