Viessmann FB2B Installation And Service Instructions Manual page 105

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
51
No DHW heating
58
No DHW heating
59
No DHW heating
92
No DHW heating
94
No solar DHW heat-
ing
9A
No solar DHW heat-
ing
9C
No solar DHW heat-
ing
9E
Control mode
9F
Control mode
A2
Emergency mode in
case of insufficient
system pressure
Cause
Measures
Short circuit, outlet
Check sensors (see
temperature sen-
page 117)
sor
Lead break, cylin-
Check sensors (see
der temperature
page 117)
sensor
Lead break, outlet
Check sensors (see
temperature sen-
page 117)
sor
Short circuit, col-
Check sensor & to the
lector temperature
solar control module.
sensor (connection
to the solar control
module)
Short circuit, cylin-
Check sensor % to the
der temperature
solar control module.
sensor (connection
to the solar control
module)
Lead break, collec-
Check sensor & to the
tor temperature
solar control module.
sensor (connection
to the solar control
module)
Lead break, cylin-
Check sensor % to the
der temperature
solar control module.
sensor (connection
to the solar control
module)
No flow rate in the
Check solar circuit pump
collector circuit or
and solar circuit. Acknowl-
flow rate too low, or
edge fault message.
temperature limiter
has responded
Solar control mod-
Replace solar control
ule fault
module
System pressure
Top up with water
too low
Troubleshooting
105