Viessmann FB2B Installation And Service Instructions Manual page 68

4.8 to 26 kw gas condensing/solar storage combi boiler natural gas and lpg version gas council no.: 47-819-18 19 kw 47-819-19 26 kw
Table of Contents

Advertisement

Code 1
General
(cont.)
Coding in the delivered condition
Internal circulation pump function
51:0
System with low loss
header:
Internal circulation pump
always starts when there
is a heat demand.
Subscriber no.
77:1
LON subscriber number
Detached house/apartment building
7F:1
Detached house
Lock out controls
8F:0
All control elements
active
68
Possible change
51:1
System with low loss
header:
When there is a heat
demand, the internal circu-
lation pump will only be
started when the burner is
operational.
51:2
System with heating water
buffer cylinder:
When there is a heat
demand, the internal circu-
lation pump will only be
started when the burner is
operational.
77:2
LON subscriber number,
to
adjustable from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number only
once.
7F:0
Apartment building
Separate adjustment of
holiday program and time
program for DHW heating,
as option
8F:1
All control elements locked
out
8F:2
Only standard settings can
be controlled