Technical Specifications - Siemens SITRANS P250 Operating Instructions Manual

Differential pressure transmitter
Table of Contents

Advertisement

Available languages

Available languages

Technical specifications

SITRANS P250 (7MF1641) Technical data
Applications
Differential pressure
Liquids and neutral gases
measurement
Mode of operation
Measuring principle
Piezoresistive measuring cell (ceramic diaphragm)
Input
Measured variable
Differential pressure
Measuring range
0 ... 0.1 to 0 ... 25 bar
(0 ... 1.45 to 0 ... 363 psi)
Operating pressure
≤ 25 bar at a differential pressure range < 6 bar
≤ 50 bar at a differential pressure range > 10 bar
Burst pressure
1.5 x system pressure
Output
Output signal
Current output signal
4 ... 20 mA
Voltage output signal
0 ... 5 VDC and 0 ... 10 VDC
Load
3-wire
> 10 kΩ
2-wire
≤ (UH - 11 V) / 0.02 A
Measuring accuracy
Dynamic behavior
≤ 1% of full scale value - typical,
(at 25°C / 77°F, including
see table " Maximum permitted pressure ranges"
conformity error, hysteresis,
and repeatability)
Long-term drift in accordance
≤ 0.5 % of full scale value
with IEC 60770
Ambient temperature influence
Start of scale value
≤ 0.6 % / 10K of full scale value (≤ 1.2 % / 10K with
measuring cell 0 ... 0.1 bar (1.45 psi))
Full scale value
≤ 0.22 % / 10K of full scale value (≤ 0.37 % / 10K with
measuring cell 0 ... 0.1 bar (1.45 psi))
Dynamic behavior
Suitability for static and dynamic measurements
Response time T99
< 5 ms
Load alternation
< 50 Hz
Conditions of use
Ambient conditions
Process temperature
- 15 ...+ 85 °C (5 ... 185 °F)
Ambient temperature
- 15 ...+ 85 °C (5 ... 185 °F)
Storage temperature
- 40 ...+ 85 °C (-40 ... +185 °F)
Degree of protection to
IP65
EN 60529
Mounting position
Any
Installation
Fastening bracket, included
Construction
Weight
approximately 430 g (c. 0.95 lb)
Housing material
Stainless steel 1.4305/AISI 303 m
Electrical connection
Process connection
Material of the wetted parts
Process connection
Stainless steel 1.4305/AISI 303, CuZn nickel-plated
Diaphragm
Ceramics Al2O3 (96 %)
Sealant
FPM (standard), EPDM, NBR, MVQ, CR
Auxiliary power
UH Terminal voltage on pressure transducer
2-wire, 4 ... 20 mA
11 ... 33 VDC
3-wire, 0 ... 5 VDC
11 ... 33 VDC/24 VAC ± 15 %
SITRANS P250 (7MF1641)
A5E02135036-01, 05/2008
Plug connector DIN EN 175301-803-A
Round plug DIN EN 60130-9
Cable 1.5 m
Hose tailpiece Ø 4 mm/6 mm
Pipe union Ø 6 mm/ 8 mm
Male thread 7/16-20 UNF, G1/8
Female thread 1/8-27 NPT (standard), G1/8
SITRANS P250 (7MF1641) Technical data
3-wire, 0 ... 10 VDC
18 ... 33 VDC/24 VAC ± 15 %
Current consumption at rated pressure
2-wire
< 20mA
3-wire
< 5mA
Reverse polarity protection
Short circuit and reverse polarity protected Every
connection to every other one with max. supply
voltage.
Certificates and approvals
Approval
CE conformity
Maximum permissible pressure ranges
Measuring range
Maximum permitted operating
pressure
[bar]
[psi]
(at one side)
0... 0,1
0...1.45
0.6 bar
(8.7 psi)
0... 0,2
0...2.9
0.6 bar
(8.7 psi)
0...
0...3.63
0.6 bar
0,25
(8.7 psi)
0... 0,3
0...4.35
0.6 bar
(8.7 psi)
0... 0,4
0...5.8
1.2 bar
(17.4 psi)
0... 0,5
0...7.25
1.2 bar
(17.4 psi)
0... 0,6
0...8.7
1.2 bar
(17.4 psi)
0... 1,0
0...14.5
2 bar (29 psi)
0... 1,6
0...23.2
3.2 bar
(46.4 psi)
0... 2,5
0...36.3
5 bar
(72.5 psi)
0... 4
0...58
8 bar (116 psi)
0... 6
0...87
12 bar
(174 psi)
0... 10
0...145
20 bar
(290 psi)
0... 16
0...232
32 bar
(464 psi)
0... 25
0...363
50 bar
(725 psi)
Burst
pressure
measurement
(at both sides)
25 bar (363 psi)
37.5 bar
≤ 1,0 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,8 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,8 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
25 bar (363 psi)
37.5 bar
≤ 0,5 %
(544 psi)
50 bar (725 psi)
75 bar
≤ 0,5 %
(1088 psi)
50 bar (725 psi)
75 bar
≤ 0,5 %
(1088 psi)
50 bar (725 psi)
75 bar
≤ 0,5 %
(1088 psi)
Deviating
3

Advertisement

Table of Contents
loading

Table of Contents