9.3.2 Replacing Fuses

Eaton NCL fuses are normally provided when
the fuse truck is built unless otherwise specified.
However, any Class L current limiting fuse of the proper
current rating can be used as a replacement.
After the fuse truck has been withdrawn from the com-
partment, the fuses can be removed by unbolting them
from the conductors on the fuse truck. This is a relatively
uncomplicated procedure on the DS-4000 fuse truck
because there is sufficient working space within the
truck. However, because the DS-3200 fuse truck is more
restricted in space it will facilitate the operation if the front
cover and levering mechanism is first removed from the
truck (see Figure 83).
After replacing fuses, be sure that all connection bolts are
tight and that any truck parts removed in the process
have been replaced.
Instruction Booklet IB 33-790-1J
Fig. 81 DS-3200 Fuse Truck Front View.

9.3.3 Blown Fuse Indicator

The same Blown Fuse Indicator is provided on fuse
trucks as on DSL circuit breakers. However, since there is
no opening mechanism on fuse trucks, it cannot serve
directly as an anti-single phase device. In order to per-
form this function, the Blown Fuse Indicator is arranged
to mechanically operate a switch, which is wired to sec-
ondary contacts on the fuse truck. The switchgear
assembly wiring must be arranged to connect this switch
into the tripping circuit of the associated circuit breaker
(see Figure 83). Again, the indicator must be reset after
being operated to reset the switch; or its contact will pre-
vent the breaker from being closed.
EaToN CorPoraTIoN www.eaton.com
Effective November 2010
71