Commissioning
4.2 Commissioning
Table 4- 15
Analog outputs
Parameter
Terminals
CU240B-2
p0771[0]
12 / 13
p0771[1]
-
p0776[0, 1]
Analog outputs, type
Table 4- 16
Changing the function of an analog output
Changing the function
1. Select the required function marked using a "CO" parameter.
2. Set parameter p0771 of the analog output to the value of the
"CO" parameter.
Use parameter p0776[0] to configure the analog input as voltage or current input.
Table 4- 17
Motor temperature sensor interface
Parameter
Terminal
p0601
14
15
p0604
Motor temperature alarm threshold
52
Terminals
Terminals
CU240E-2
CU230P-2
12 / 13
12 / 13
26 / 27
26 / 27
Abbreviation
Possible setting
T1 motor (+)
0: No sensor (factory setting)
1: PTC thermistor (→ P0604)
T2 motor (-)
2: KTY84 (→ P0604)
4: ThermoClick sensor
Signal
Setting
AO 0
Important status signals:
0: Analog output locked
AO 1
21: Speed actual value
24: Output frequency smoothed
25: Output voltage smoothed
26: DC link voltage smoothed
27: Actual current value (smoothed absolute value)
0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
Examples
Function
: Signal "Current" at AO 0.
Setting
: p0771 = 27
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 11/2013, A5E32885834B AA