Operator Level 1; Level 1 Operator Parameters; Operator Level 2; To Enter Level 2 - ACS 3200 Series Custom Manual

Pid temperature controllers
Hide thumbs Also See for 3200 Series:
Table of Contents

Advertisement

4. Operator Level 1

4.1.1

Level 1 Operator Parameters

A minimal list of parameters are available in operator Level
1 which is designed for day to day operation. Access to
these parameters is not protected by a pass code.
Press
to step through the list of parameters. The
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
or
to adjust this value. If no key is
pressed for 30 seconds the controller returns to the HOME
display
The parameters that appear depend upon the functions
configured. They are:-
Home List
Parameter
Scrolling Display
Mnemonic
and Description
WRK.OP
WORKING
OUTPUT
The active output
value
A.TUNE
AUTO TUNE
Activate Auto
Tune Of PID
Loop.
SP1
SETPOINT 1
SP2
SETPOINT 2
T.REMN
TIME
REMAINING
Time to end of set
period
DWELL
SET TIME
DURATION
Timer set time
DEC.P
DECIMAL
POINT
UNITS
DISPLAY
UNITS
PB
PROPORTIONAL
BAND
TI
INTEGRAL
TIME
TD
DERIVATIVE
TIME
R2G
RELATIVE
COOL GAIN
OP.HI
OUTPUT
HIGH LIMIT
ADDR
COMMS
ADDRESS
8
Alterability
Read only.
Appears when the
controller is in AUTO or
OFF mode.
In a motorised valve
controller (option VC or
VP) this is the 'inferred'
position of the valve
Alterable
Alterable
Alterable
Read only
0:00 to 99.59 hh:mm or
mm:ss
Alterable. Only shown if
timer (not programmer)
configured.
Read only
Read Only
Alterable
Alterable
Alterable
Read Only
Read Only
Read Only

5. Operator Level 2

Level 2 provides access to additional parameters. Access to
these is protected by a security code.
5.1

To Enter Level 2

1.
From any display press and hold
2.
After a few seconds the display will
show:-
.
3.
Release
(If no button is pressed for about 45 seconds the display
returns to the HOME display)
4.
Press
or
choose Lev 2 (Level 2
5.
After 2 seconds the
display will show:-
6.
Press
or
pass code. = '101'
If an incorrect code is entered the controller reverts to
Level 1.
5.2

To Return to Level 1

1.
Press and hold
to select LEv 1
2.
Press
The controller will return to the level 1 HOME display.
Note: A security code is not required when going from a
higher level to a lower level.
5.3

Level 2 Parameters

Press
to step through the list of parameters. The
mnemonic of the parameter is shown in the lower display.
After five seconds a scrolling text description of the
parameter appears.
The value of the parameter is shown in the upper display.
Press
or
to adjust this value. If no key is
pressed for 30 seconds the controller returns to the HOME
display
Backscroll is achieved when you are in this list by pressing
while holding down
The following table shows a list of parameters available in
Level 2.
3200 Series
.
to
to enter the
.
ACS 3216 Operators Manual