Master Parameter List - ACS 3200 Series Custom Manual

Pid temperature controllers
Hide thumbs Also See for 3200 Series:
Table of Contents

Advertisement

3200 Series
7.1.1

Master Parameter List

INPUT LIST
I N P U T
Name
Scrolling Display
I N . T Y P
INPUT TYPE
U N I T S
DISPLAY UNITS
D E C . P
DISPLAY
POINTS
M V . H I
LINEAR INPUT
HIGH
M V . L o
LINEAR INPUT
LOW
RNG.HI
RANGE HIGH
LIMIT
RNG.LO
RANGE LOW
LIMIT
PV.OFS
PV OFFSET
F I L T . T
FILTER TIME
C J . t y p
CJC TYPE
S B . t y p
SENSOR BREAK
TYPE
C J C . i n
CJC
TEMPERATURE
P v . i n
PV INPUT
VALUE
m v . i n
MILLIVOLT
INPUT VALUE
INPUT/OUTPUT LIST 1 'I O -1 '
Name
Scrolling Display
1..i d
I/O 1 TYPE
1.FUNC
I/O 1 FUNCTION
ACS 3216 Operators Manual
Parameter Description
Selects input linearisation and range
Display units shown on the
instrument
Decimal point position
High limit for mV (mA) inputs
Low limit for mV (mA) inputs
Range high limit for thermocouple
RTD and mV inputs
Range low limit for thermocouple
RTD and mV inputs
A simple offset applied to all input
values.
Input filter time
Configuration of the CJC type
Defines the action which is applied
to the control output if the sensor
breaks (open circuit).
Temperature measured at the rear
terminal block. Used in the CJC
calculation
Current measured temperature
Millivolts measured at the rear PV
Input terminals
Parameter Description
I/O channel 1 hardware type
defined by the hardware
fitted
I/O channel function.
If the instrument is ordered
as valve positioner (codes
VC or VP), only options
available are , none,
d.out, UP, or dwn
Note: If output 1 is set to
Up ensure the other valve
position output is set to
dwn and vice versa
Value
See manufacture manual for input types available
none
No units - only for custom linearisation
o
C
Celsius
o
F
Fahrenheit
o
k
Kelvin
PErc
%
nnnn
No DP
nnn.n
One DP
nn.nn
Two DP
-10.00 to +80.00mV
-10.00 to +80.00mV
From the high limit of the selected input type to the
'Low Range Limit' parameter minus one display unit.
From the low limit of the selected input type to the
'High Range Limit' parameter minus one display unit.
Generally one decimal point more than PV
OFF to 100.0 seconds
Auto
Automatic
0
C
o
o
Fixed at 0
C
50
C
o
o
Fixed at 50
C
oFF
No sensor break will be detected
on
Open circuit sensor will be detected
Lat
Latching
Read only
Minimum display to maximum display range
xx.xx mV - read only
Value
none
No input or output fitted
dC.OP
DC output
ReLy
Relay output
L.IO
Logic Input/Output
SSR
Triac output
none
Disabled. If disabled no further
parameters are shown
d.out
Digital output
UP
Valve open codes VC and VP only
dwn
Valve close codes VC and VP only
Heat
Heat output
CooL
Cool output
d.in
Digital input if '1.i d ' = 'L.IO
w.SP
Working setpoint re-transmission
PV
Process variable re-transmission
OP
Output power demand re-transmission
Default
Access Level
Conf
L3 R/O
o
C
L3
nnnn
Conf
L3 R/O
80.00
Conf
-10.00
Conf
Conf
L3 R/O
Conf
L3 R/O
L3
1.6
L3
Auto
Conf and if
T/C
L3 R/O
on
Conf
L3 R/O
Conf
L3 R/O and
if T/C
Conf
L3 R/O
Conf
L3 R/O
Default
Access Level
As
Read only
ordered
HEAt
Conf
Shown if I/O 1 TYPE =
dc.OP Retransmission
13