8. Diagnostic Alarms

Diagnostic alarms indicate a possible fault within the controller or connected devices.
Display shows
E.Conf
A change made to a parameter takes a finite time to be
entered. If the power to the controller is turned off
before the change has been entered then this alarm will
occur.
Do not turn the power off to the controller while ConF
is flashing
E.CaL
Calibration error
E2.Er
EEPROM error
EE.Er
Non-vol memory error
E.Lin
Invalid input type. This refers to custom linearisation
which may not have been applied correctly or may have
been corrupted.
Emod
IO1, OP2, or OP3 has been changed
20
Parameter
Value
Description
To select low and high
IdLe
offset state or reset to no
Lo
offsets.
Hi
rEST
To set an offset value.
-1999 to 9999
To calibrate low and high
none
offset
0
50
150r
400r
CJC
Ct 0
Ct 70
Fact
Ima.L
Ima.H
2ma.L
2ma.H
3ma.L
3ma.H
rm.VL
rm.VH
rm.CL
rm.CH
NO
To start the calibration
sequence
Yes
Busy
Pass
faiL
What it means
Normal operating state
Low offset
High offset
Remove high and low offsets
Not selected
Select mV low calibration point
Select mV high calibration point
Select PRT low cal point
Select PRT high cal point
Select CJC calibration
Select CT low cal point
Select CT high cal point
Return to factory settings
Low mA output from I/O 1
High mA output from I/O 1
Low mA output from output 2
High mA output from output 2
Low mA output from output 3
High mA output from output 3
Remote setpoint input low volts
Remote setpoint input high volts
Remote setpoint input low current
Remote setpoint input high current
Start
Calibrating
Calibration successful
Calibration unsuccessful
What to do about it
Enter configuration mode then return to the required
operating mode. It may be necessary to re-enter the
parameter change since it will not have been entered in
the previous configuration.
Re-instate Factory calibration
Return to factory for repair
Note the error and contact your supplier
Go to the INPUT list in configuration level and set a
valid thermocouple or input type
If this has been field changed by the installation of a
new board, enter config level, then exit back to operator
level.
If the message occurs at any other time return to factory
for repair.
3200 Series
Default
Access Level
IdLE
L3 only
L3 only
none
Conf only
NO
Conf only