Modbus Parameter Addresses

Parameter
Mnemonic
PV.IN
PV (Temperature) Input Value (see also Modbus address 203 which allows writes over Modbus to this variable).
TG.SP
Target Setpoint.
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
MAN.OP
Manual Output Value
WRK.OP
Working Output
WKG.SP
Working Setpoint (Read Only)
PB
Proportional Band
Ti
Integral Time
(0 = No Integral Action)
Td
Derivative Time
(0 = No Derivative Action)
A1.---
Alarm 1 Threshold
A2.---
Alarm 2 Threshold
T.STAT
Timer Status
0 = Reset
1 = Run
2 = Hold
3 = End
SP1
Setpoint 1
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
SP2
Setpoint 2
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
OP.HI
Output High Limit
OP.LO
Output Low Limit
SP.RAT
Setpoint Rate Limit Value (0 = no rate limit)
StAt
Instrument Status. This is a bitmap:
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B4 – Auto/Manual Status
B5 – Sensor Break Status
B6 – Loop Break Status
B7 – CT Low load current alarm status
B8 – CT High leakage current alarm status
B9 – Program End
B10 – PV Overrange (by > 5% of span)
B11 – CT Overcurrent alarm status
B12 – New Alarm Status
B13 – Timer/Ramp Running
B14 – Remote (comms) SP Fail
B15 – Autotune Status
In each case, a setting of 1 signifies 'Active', 0 signifies 'Inactive'.
A3.---
Alarm 3 Threshold
A4.---
Alarm 4 Threshold
Home Display.
Home
0 – Standard PV and SP display
1 – PV and Output Power display
2 – PV and Time remaining display
3 – PV and Timer elapsed time display
4 – PV and Alarm 1 setpoint
5 – PV and Load Current
6 – PV only
7 – PV and Composite SP/Time remaining
24
Parameter Name
3200 Series
Modbus Address
1
2
3
4
5
6
8
9
13
14
23
24
25
30
31
35
75
81
82
106