Operation and Display
4.3 Key Definition
1
NO.
Symbol
5
Note
Password level (1 bit, 0 to 2) and password (6 bits) should be entered at first for key setting. Password level
and permission:
• L0 password-all parameters above are configurable;
• L1 password-all parameters above are configurable;
• L2 password-all parameters except for meter reset, clearing extreme value and PT/CT conversion ratio are
configurable. All default password is 000000.
Note
The meter should be reset after altering PT/CT ratio to ensure reasonable correspondence between
communication reading and displayed metering data.
3. Parameter setting with keys (take "Conn communication setting" for example)
Figure 4-2
28
st
level menu
Definition
Symbol
Display
setting
Parameter setting with keys
nd
2
level menu
Definition
Time of returning to
cyclic display state
when no operation
Time of backlight
on when no opera-
tion (normally on
when set to 0)
Interval of cyclic
display
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
Range
Remarks
Unit: min.
1 ... 99
Default setting: 10
Unit: min.
0 ... 99
Default setting: 10
Unit: sec
1 ... 99
Default setting: 5