Emerson Bettis RTS CL Series User Instructions page 61

Compact linear electric actuator
Table of Contents

Advertisement

User Instructions
MAN-02-04-60-0350-EN Rev. 3
Table 22.
P14.12
P14.13
P14.14
P14.15
P14.16
P14.17
P14.18
from firmware 1.338
5)
from firmware 1.340
6)
up to firmware 1.337
7)
up to firmware 1.337
8)
Parameter Menu
PID Controller Parameter Group (2)
Sub Menu
Menu Item
Item
Live zero
PID-contoller
detect.
Caiibration
PID-controller
of ext. actual
value
PID-controller Process begin
PID-controller Process begin
Process
PID-controller
comma shift
PID-controller Process unit
PID-controller Dead band
Poss.
Notes / Comments
Setting
The monitoring of the external actual value is
0: Ignore
disabled
Actuator stops on signal failure of external. actual
1: Stop
value
On signal failure of external actual values, actuator
2: Open
moves to the OPEN position.
On signal failure of external actual values, actuator
3: Closed
moves to the CLOSED position
On signal failure of external actual values, actuator
4: Emergency
moves to the EMERGENCY position
position
(see param P13.7)
5: Emergency
Reserved for future use
PID
Calibration process: By applying 20mA to the
-10.0 – 10.0%
external actual value input, this parameter is
corrected until the readout matches 20 mA
-32768 -
Mantissa of the real process variable (begin of
+32767
external actual value)
-32768 -
Mantissa of the real process variable (end of external
+32767
actual value)
Position of the comma for process begin/end
-3 - 3
(P14.14, P14.15), e.g.: mantissa = 200, comma shift
= -2/2, process value = 2.00/20000
--
Unit of the real process variable
0.1 - 10.0%
Tolerance range for the control deviation (set point –
{1.0%}
external actual value) where no adjustment occurs.
Section 7: Parameter Menu
February 2019
7)
56