  • Page 1 Installation and Operation Manual HOT WATER STORAGE TANKS RBC 200, RBC 300, RBC 400, RBC 500, RBC 750, RBC 1000, RBC 1500, RBC 2000, RBC 2500 and RBC 3000 RBC 200 - 3000...
  • Page 2: Table Of Contents

    5 Examples of Assigning Connection Points ................... 6 Installation and Commissioning ....................7 Tank Insulation ..........................8 Maintenance, Replacement of Magnesium Anode Bar ..............9 Disposal ............................10 Warranty ............................REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 3: Description

    2× lateral with G 5/4“ inner thread, to the heating coil 2× lateral with G 5/4“ inner thread (RBC 200, RBC 300 and RBC 400 with G 1“ inner thread, RBC 1500 - 3000 with G 2“ inner thread) for cold water inlet and hot water outlet 2×...
  • Page 4: Technical Data And Dimensions Of Rbc Models

    Max. working temperature - heat exchanger ............110 °C Max. working pressure - tank ................10 bar Max. working pressure - heat exchanger ............. 10 bar DHW heating ∆t =35 °C (80/60 - 10/45) - coil ............f REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 5: Operation

    DHW auxiliary heating. Hot water temperature should be set to 60-65 °C. This temperature guarantees the best operation and at the same time, it prevents formation of Legionella bacteria. REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 6: Examples Of Assigning Connection Points

    3-way z.v. cold water Example II. A larger solar surface - enlarged Enlarged solar heat transfer surface area. heat transfer surface area bb bbb recirculation cold water 3-way z.v Pool REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 7 Table of limit values for total dissolved solids in hot water Description Total dissolved solids (TDS) Chlorides Max. value 6.5 - 9.5 600 mg/l 40 mg/l 100 mg/l 20 mg/l 200 mg/l 0,2 mg/l REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 8: Installation And Commissioning

    In order to prevent water loss, an expansion tank should be installed at the cold water inlet as well (8 l volume for RBC 200, 12 l volume for RBC 300 and 400, 18 l volume for RBC 500, 24 l volume for RBC 750, 35 l volume for RBC 1000, 60 l volume for RBC 1500, 80 l volume for RBC 2000, 100 l volume for...
  • Page 9: Tank Insulation

    ○ defects caused by mechanical damage to the product, ○ defects caused by tampering or incompetent repair. REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 10: Maintenance, Replacement Of Magnesium Anode Bar

    This product is covered by warranty according to the conditions described in this Manual and according to the Warranty Certificate. A Warranty Certificate is an integral part of the supply. Tank transport or storing in a hori- zontal position is considered a warranty violation! REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 11 REGULUS - RBC Hot Water Storage Tanks - www.regulus.eu │...
  • Page 12 ©2019 We reserve the right to errors, changes and improvements without prior notice. REGULUS spol. s r.o. E-mail: sales@regulus.eu Web: www.regulus.eu...