2.4 Parameter Setting

Value
Ä The following table shows the bit positions of the value to be written to address 2F0Dh to
achieve the correspondent functions.
Value
8 ... 15
2.4
Parameter Setting
Using the Modbus® protocol it is possible to access the menu parameters. In the following
tables it is reported the numerical range for each parameter. To correctly understand the
correspondence between the numeric value and the selected function and/or the unit of
measure, please see the ATC operating manual. To make effective the changes made to setup
parameters it is necessary to store the values in EEPROM, using the dedicated command
described in table 3.
2.5

Setup Parameters

(To be used with functions 04 and 06)
ADDRESS WORDS
3000h
3001h
3002h
3003h
3004h
3005h
3100h
3101h
3102h
3103h
3104h
3105h
3106h
3107h
3108h
22
0
Keyboard unlock
1
Keyboard lock
0
Line 2 manual switching
1
OFF mode
2
MAN mode
3
AUT mode
4
TEST mode
5
Line 1 manual switching
6
Line 2 measure selection
7
Line 1 measure selection
Not used
1
P1.01 Nominal voltage
1
P1.02 VT ratio
1
P1.03 Wiring configuration
1
P1.04 Voltage control mode
1
P1.05 Nominal frequency
1
P1.06 Nominal battery voltage
1
P2.01 Application type
1
P2.02 Phase sequence control
1
P2.03 Priority line selection
1
P2.04 Line1 → Line2 interlock time
P2.05 Line2 → Line1 interlock time
1
1
P2.06 Transfer strategy
1
P2.07 Switch command mode
1
P2.08 Switch open / close timeout
1
P2.09 Switch open pulse duration
Function
Keystroke simulation
PARAMETER
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
RANGE
FORMAT
100 ...690
Unsigned integer
100 ...999
Unsigned integer
0 ...3 ¿
Unsigned integer
0 ...2 ¿
Unsigned integer
0 ...1 ¿
Unsigned integer
0 ...3 ¿
Unsigned integer
0 ...2 ¿
Unsigned integer
0 ...2 ¿
Unsigned integer
0 ...1 ¿
Unsigned integer
100 ...900
Unsigned integer
100 ...900
Unsigned integer
0 ...1 ¿
Unsigned integer
0 ...2 ¿
Unsigned integer
1 ...900
Unsigned integer
1 ...600
Unsigned integer
ATC5300