Siemens ATC5300 Manual page 20

Automatic transfer controller
Hide thumbs Also See for ATC5300:
Table of Contents

Advertisement

Data Library
2.2 Status Bits
 Following table shows meaning of bits of the word at address 2074h (Line 1) and 2076h
(Line 2):
Bit
10
11
12
13
14 ... 15
à Following table shows meaning of bits of the word at address 2074h (Line 1) and 2076h
(Line 2):
Bit
6 ... 15
Ä Following table shows meaning of bits of the word at address 2078h:
Bit
10
12
13
14 ... 15
20
0
Line values into limits
1
Line values into limits delayed
2
Voltage into limits
3
Voltage ok
4
Frequency into limits
5
Frequency ok
6
Voltage below min
7
Voltage above max
8
Voltage asymmetry
9
Voltage phase loss
Frequency below min
Frequency above max
Wrong phase sequence
All line parameters ok
Not used
0
Breaker closed
1
Trip alarm
2
Withdrawn alarm
3
Command status (1 = close)
4
Close command output
5
Open command output
Not used
0
Line 1 breaker closed feedback
1
Line 1 breaker trip
2
Line 1 breaker Withdrawn
3
Line 2 breaker closed feedback
4
Line 2 breaker trip
5
Line 2 breaker Withdrawn
6
Transfer to secondary line
7
Inhibit return to main line
8
Emergency pushbutton
9
Generator start
Generator 1 ready
11
Generator 2 ready
Keyboard locked
Lock parameters
Not used
Line Status
Breaker Status
Input Functions Status
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02