Primary Element Location; Primary Element Orientation - Emerson Rosemount 1495 Quick Start Manual

Orifice plate/flange union

Advertisement

February 2014
Step 1: Primary element location
To obtain published accuracy for a 1495 Orifice Plate, sufficient straight run is
required to produce a fully developed flow profile. Please see Appendix B of the
Rosemount 1495 Orifice Plate Manual (00809-0100-4792) for a list of required
straight pipe recommendations based on ISO 5167, AGA Report No. 3, and ASME
MFC 3M Standards. Shorter straight runs are possible, but accuracy will be
affected per the Standards. Consult the Factory for further information.
Step 2: Primary element orientation
Horizontal pipe installation
Recommended
Zone 120 degrees
30 degrees
Gas
30 degrees
45 degrees
Recommended
Zone 90 degrees
Liquid
45 degrees
Quick Start Guide
Steam
3