Technical Specifications Of The Cpu 414-3; (6Es7414-3Xj00-0Ab0) - Siemens SIMATIC S7-400 Reference Manual

Automation system
Hide thumbs Also See for SIMATIC S7-400:
Table of Contents

Advertisement

Technical Specifications
4.4
Technical Specifications of the CPU 414-3;
(6ES7414-3XJ00-0AB0)
CPU and Version
MLFB
Firmware version
Associated programming
package
Memory
Working memory
Integrated
Expandable
Load memory
Integrated
Expandable FEPROM
Expandable RAM
Backup
With battery
Without battery
Processing Times
Processing times for
Bit operations
Word instructions
Integer math
instructions
Floating-point math
instructions
Timers/Counters and Their Retentivity
S7 counters
Retentivity can be set
Preset
Counting range
IEC counter
Type
S7 timers
Retentivity can be set
Preset
Time range
IEC timers
Type
4-14
6ES7414-3XJ00-0AB0
V 3.1
As of STEP7 V 5.2
384 Kbytes for code
384 Kbytes for data
No
256 Kbytes RAM
With memory card (FLASH)
up to 64 Mbytes
With memory card (RAM)
up to 64 Mbytes
Yes
All data
None
Min. 0.1 ms
Min. 0.1 ms
Min. 0.1 ms
Min. 0.6 ms
256
From Z 0 to Z 255
From Z 0 to Z 7
1 to 999
Yes
SFB
256
From T 0 to T 255
No retentive timers
10 ms to 9990 s
Yes
SFB
Data Areas and Their Retentivity
Total retentive data areas
Total working and load
(including memory bits;
memory (with backup
times; counts)
battery)
Memory markers
8 Kbytes
Retentivity can be set
From MB 0 to MB 8191
Preset retentivity
From MB 0 to MB 15
Clock memories
8 (1 memory byte)
Data blocks
Max. 4095 (DB 0 reserved)
Size
Max. 64 Kbytes
Local data (can be set)
Max. 16 Kbytes
Preset
8 Kbytes
Blocks
OBs
See instruction list
Size
Max. 64 Kbytes
Nesting depth
Per priority class
24
Additionally in an error
2
OB
FBs
Max. 2048
Size
Max. 64 Kbytes
FCs
Max. 2048
Size
Max. 64 Kbytes
Address Areas (Inputs/Outputs)
Total I/O address area
8 Kbytes/8 Kbytes
Of which distributed
MPI/DP interface
2 Kbytes/2 Kbytes
DP interface
6 Kbytes/6 Kbytes
The distributed I/O address area is halved for each strand
operated clock synchronously, i.e. in which an OB 61 to
OB 63 is assigned.
Process Image
8 Kbytes/8 Kbytes
(can be set)
Preset
256 bytes/256 bytes
Number of partial
Max. 8
process images
Consistent data
Max. 244 bytes
Digital channels
65536/65536
Of which central
65536/65536
Analog channels
4096/4096
Of which central
4096/4096
Automation System S7-400 CPU Specifications