Technical Specifications
Communication Functions
Programming device/OP
communication
Number of connectable
OPs
Number of connection
resources for S7
connections via all
interfaces and CPs
Global data communication Yes
Number of GD circuits
Number of GD
packages
Sender
Receiver
Size of GD packages
Of which consistent 1 variable
S7 basic communication
User data per job
Of which consistent 16 Byte
S7 communication
User data per job
Of which consistent 1 variable (462 bytes)
S5-compatible
communication
User data per job
Of which consistent 240 bytes
Standard communication
(FMS)
Interfaces
1st Interface
Type of interface
Physical
Isolated
Power supply to interface
(15 VDC to 30 VDC)
Number of connection
resources
Functionality
MPI
PROFIBUS DP
MPI
Utilities
Programming
device/OP
communication
Routing
Global data
communication
S7 basic
communication
S7 communication
Transmission rates
4-16
Yes
31 without message
processing, 8 with message
processing
32, with one each of those
reserved for PG and OP
Max. 8
Max. 8
Max. 16
Max. 64 bytes
Yes
Max. 76 bytes
Yes
Max. 64 Kbytes
Yes (via CP – max. 10 –
and FC AG_SEND and FC
AG_RECV)
Max. 8 Kbytes
Yes (via CP and loadable
FB)
Integrated
RS 485/Profibus
Yes
Max. 150 mA
MPI: 32
DP: 16
Yes
DP master/DP slave
Yes
Yes
Yes
Yes
Yes
Up to 12 Mbps
DP Master
Utilities
Programming
Yes
device/OP
communication
Routing
Yes
Equidistance
Yes
SYNC/FREEZE
Yes
Enable/disable DP
Yes
slaves
Transmission rates
Up to 12 Mbps
Number of DP slaves
Max. 32
Address area
Max. 2 Kbytes inputs/2
Kbytes outputs
User data per DP slave
Maximum 244 bytes E,
maximum 244 bytes A,
distributed over 244 slots
each with 128 bytes
DP slave
Utilities
Monitor/modify
Yes, if the interface is active
Yes, if the interface is active
Programming
Yes, if the interface is active
Routing
DDB (GSD) file
http://www.ad.siemens.de/c
si_e/gsd
Transmission rate
Up to 12 Mbps
Intermediate memory
244 bytes inputs/ 244 bytes
outputs
Address areas
Max. 32
User data per
Max. 32 bytes
address area
32 bytes
Of which consistent
2nd Interface
Type of interface
Integrated
Physical
RS 485/Profibus
Isolated
Yes
Power supply to interface
Max. 150 mA
(15 VDC to 30 VDC)
Number of connection
16
resources