Optional Installation Components - Siemens 6DL2804 Series Hardware Installation Manual

Distributed i/o device
Table of Contents

Advertisement

4.4

Optional installation components

The following separately certified components can be installed optionally:
● Terminals:
● Temperature sensors:
● Relays, disconnectors and fuses:
● Command and signaling devices:
● FO couplers:
● Lightning protection components:
● Heater:
● Modular electro-pneumatic automation system AirLine Ex (type 8650, from the company
● When installing a pneumatic system, exit the air passing through the exhaust connections
Distributed I/O device 6DL2804-xxxxx
Siemens Controls
Hardware Installation Manual, 03/2014, A5E00378896F-03
– Ex e for the connection of cable cross-sections >4 mm,
– Ex i for wiring of intrinsically safe signals (blue); these may only be used for Ex i
signals.
Make sure when arranging intrinsically safe and non-intrinsically safe terminals that they
are separated ("thread measure") by at least 50 mm.
For monitoring the temperature inside the enclosure,
For interrupting, switching or protecting individual signal circuits.
For manual switching (control switch) or optical display (indicator lamps) in the enclosure
wall.
For connecting the PROFIBUS of the ET 200iSP by means of FO cable
For protecting the ET 200iSP components from lighting strikes when the enclosure is
installed in exposed locations.
To prevent condensation in the enclosure at low temperatures, it is recommendable to
install a heater. The heater must be dimensioned in accordance with the enclosure size.
A heater permits operation of the devices at temperatures below -20 °C.
Note
If components with a supply voltage of 120 / 230 V AC are installed, you must fuse these
devices according to DIN 41571 and/or IEC 60127 or in accordance with the
manufacturer's data.
Bürkert):
Connected to the ET 200iSP components to form an automation system for processing
electrical and pneumatic variables.
When connecting and operating, observe the manufacturer's descriptions and manuals.
out of the enclosure.
NOTICE
Damage to seal or screwed glands
Make sure that the vent of the pneumatic system does not blow directly into the
enclosure. The pressure resulting in the enclosure would otherwise damage the seal
and screwed glands, and the degree of protection would no longer be provided.
4.4 Optional installation components
Mounting
23

Advertisement

Table of Contents
loading

Table of Contents