Siemens SIMATIC ET 200S Hardware Installation And Operating Manual page 213

Distributed i/o system - fail-safe modules
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Current consumption
Power dissipation of the module
Status, Interrupts, Diagnostics
Status display
Diagnostic Functions
Data for Selecting an Actuator*
Output current
Contact wiring (internal)
Wire break monitoring
Parallel connection of 2 outputs
Digital input control
Switching frequency
Limitation (internal) of the voltage induced on the
circuit interruption
Short-circuit protection of output
Time, Frequency
Switching time
Release time
Protection against Overvoltage
Protection of outputs from surge load in
accordance with IEC 61000-4-5 (no protection
elements required)
*: For more information on the requirements for sensors and actuators see
Modules."
Product Information for the Distributed I/O System ET 200S, Fail-Safe Systems Manual
Product information, 07/2006, A5E00825271-01
From backplane bus
From control voltage (IN P, IN M)
Diagnostic information can be displayed
Thermal constant current
Minimum load current
On the relay outputs
With resistive load
With inductive load according to IEC 947-5-1,
DC13
With inductive load according to IEC 947-5-1,
AC15
Symmetrical
Channel 1 (9/13) against (10/14)
Channel 2 (11/15) against (12/16)
Unsymmetrical
Channel 1 (9/13) or (10/14) against PE
Channel 2 (11/15) or (12/16) against PE
Digital Electronics Module 1 F-RO DC24V/5A AC24..230V/5A
2.6 Technical Data of the EM 1 F-RO DC24V/5A AC24..230V/5A
Technical Specifications
max. 10 mA
max. 100 mA
avg. 2.1 W
green LED
no
max. 5 A
5 mA
no
no
no
possible, no increase in load current
possible
max. 2 Hz
max. 0.1 Hz
max. 2 Hz
no
no, external fusible cutout 6 A operating class
gL/gG
avg. 13 ms
avg. 16 ms
+1 kV; 1.2/50 μs
+2 kV; 1.2/50 μs
"Wiring and Installing
2-11