Siemens 7XV5810 0BA00 Operating Instructions Manual page 15

Wide-range power supplies
Table of Contents

Advertisement

C53000-B1100-C602-1
EMC tests on interference immunity
IEC 60255-26 (Product standard)
Damped oscillatory waves
IEC 60255-26, IEC 61000-4-18, Class III
VDE 0435 part 303, Class III
Electrostatic discharge (ESD)
IEC 60255-26 Class III
EN 61000-4-2, Class III
Radiated electromagnetic fields,
amplitude modulated
IEC 61000-4-3
Radiated electromagnetic fields,
pulse modulated
IEC 61000-4-3
Fast transient disturbances/Burst
IEC 61000-4-4, Class
IEC 60255-26, Class IV
EN 61000-4-4, Class IV
Fast transient disturbances /Burst
IEC 61000-4-4, Class III
IEC 60255-26, Class III
EN 61000-4-4, Class III
7XV5810 0xA00
100 kHz and 30 surges per minute;
Test duration 1 minute
2,5 kV longitudinal voltage;
1 kV transverse voltage
6 kV contact discharge
8 kV air discharge,
both polarity; 150 pF;
Ri = 330 Ohm
10 V/m; 80 MHz to 1000MHz;
80% AM; 1 kHz
35 V/m, 900 MHz
Frequency 200 kHz;
Duty cycle 50 % oder Duty cycle 100 %
On power supply input
4 kV; 5/50 ns; 5 kHz;
Burst duration 15 ms
Repetition 300 ms; both polarity;
Ri = 50 Ohm; test duration: 1 min
On signal lines
4 kV; 5/50 ns; 5 kHz;
Burst duration 15 ms above average
Repetition 300 ms; both polarity;
Ri = 50 Ohm; test duration 1 min
Operating Instructions
Seite 15 von 20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7xv5810 0ca00

Table of Contents