Cerberus® MN7002 Power supply Description Fire & Security Products Siemens Building Technologies Group...
Page 2
Data and design subject to change without notice. / Supply subject to availability E Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche...
Additional surge protectors are only required in special cases e.g. where there is a partic- ular lightning hazard, overhead power lines etc. (see Z3I04, Z3I121). Mains back-up fuse The mains feeder must have an own and clear labelled fuse up to 10A. Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
Page 6
AX1201 225487 Battery 12V / 24Ah AX1209 462936 Battery 12V / 38Ah DMS7000 R1P061 496711 Power supply rack refer to page 12 delivered as a complete wired unit, without batteries Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
≤10A Input voltage Mains (115V ) 230V / 50...60Hz max. 220VA – – S Jumpers inserted ex factory (essential, do not remove) – Output voltage E3C021 29.6V / max. 6A Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
Quiescent current 30mA when on emergency power operation 50mA when on mains operation without battery charge Print dimensions 100 x 200 x 30mm Wire range max. 2.5mm Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
Operation with external voltage (instead of battery) – d) Operation without battery or external voltage – – Door contact simulation: X2 without jumper ex factory → Without door contact: insert jumper X2 at first E3C021. Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
– Fuse F1 / F2 / F3 blown – Input voltage >31.0V → converter malfunction – EEPROM check sum error LED ”Power on” – Input voltage >28.5V LED ”Trouble battery” – no function Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
2.44 2.42 2.40 2.38 2.36 2.34 2.32 2.30 2.28 2.26 2.24 Ua max. [V] 2.22 2.20 2.18 Ua middle [V] Ua min. [V] 2.16 2.14 2.12 2.10 [ T °C] Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
4 „Application examples”. – PTC is always required including for operation ”with external voltage” or ”without battery”. – PTC is polarity sensitive, observe the correct colour of connection wires! Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
Mounting possibilities In danger management system DMS7000 R1P061 power supply rack delivered as complete wired unit, without batteries On L-section plate of the Z1B050 mounting set E3C021 Z1B050 B2F020 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
In CZ10 fire detection system control unit 5.3.1 On G1E010 universal bracket Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
Page 18
– position one paire of batteries on YAH00’s, the other is positioned on the Z1B050 base of the control unit housing B2F020 B2F020 E3C021 E3C021 Z1B050 Z1B050 AX1201 AX1201 2x YAH00 AX1201 AX1201 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...