Cerberus® MN7002
Power supply
Description
Fire & Security Products
Siemens Building Technologies Group

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Cerberus MN7002

  • Page 1 Cerberus® MN7002 Power supply Description Fire & Security Products Siemens Building Technologies Group...
  • Page 2 Data and design subject to change without notice. / Supply subject to availability E Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche...
  • Page 3: Table Of Contents

    In CZ1-02 extinguishing system control unit ......Fire & Security Products 04.2002 Siemens Building Technologies Group...
  • Page 4 Fire & Security Products 04.2002 Siemens Building Technologies Group...
  • Page 5: Concept Of The Mn7002 Power Supply

    Additional surge protectors are only required in special cases e.g. where there is a partic- ular lightning hazard, overhead power lines etc. (see Z3I04, Z3I121). Mains back-up fuse The mains feeder must have an own and clear labelled fuse up to 10A. Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 6 AX1201 225487 Battery 12V / 24Ah AX1209 462936 Battery 12V / 38Ah DMS7000 R1P061 496711 Power supply rack refer to page 12 delivered as a complete wired unit, without batteries Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 7: Converter B2F020

    ≤10A Input voltage Mains (115V ) 230V / 50...60Hz max. 220VA – – S Jumpers inserted ex factory (essential, do not remove) – Output voltage E3C021 29.6V / max. 6A Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 8: Battery Charging Module E3C021

    Quiescent current 30mA when on emergency power operation 50mA when on mains operation without battery charge Print dimensions 100 x 200 x 30mm Wire range max. 2.5mm Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 9: Programming Switches, Jumpers

    Operation with external voltage (instead of battery) – d) Operation without battery or external voltage – – Door contact simulation: X2 without jumper ex factory → Without door contact: insert jumper X2 at first E3C021. Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 10: Led Display Block

    – Fuse F1 / F2 / F3 blown – Input voltage >31.0V → converter malfunction – EEPROM check sum error LED ”Power on” – Input voltage >28.5V LED ”Trouble battery” – no function Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 11: Floating Charging Voltage In Function Of Temperature

    2.44 2.42 2.40 2.38 2.36 2.34 2.32 2.30 2.28 2.26 2.24 Ua max. [V] 2.22 2.20 2.18 Ua middle [V] Ua min. [V] 2.16 2.14 2.12 2.10 [ T °C] Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 12: Connections Of E3C021

    4 „Application examples”. – PTC is always required including for operation ”with external voltage” or ”without battery”. – PTC is polarity sensitive, observe the correct colour of connection wires! Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 13: Application Examples

    Load 2: <2A 4– ≤4.3A Load 3: <2A 6– refer to page 8 Control unit 9– ≤6A ≤10A 115V B2F020 230V 11– 13– ≤1.7A Batteries ≤40Ah 16– 18– Control unit S3#1 S3#2 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 14: Extended Emergency Power Capacity

    B2F020 230V 11– 11– 11– 13– 13– 13– Batteries Batteries Batteries ≤40Ah ≤40Ah ≤40Ah 16– 16– 16– 18– 18– 18– Z3B220 Z3B220 Control unit S3#1 S3#1 S3#1 S3#2 S3#2 S3#2 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 15: Power Splitting

    Batt. ≤40Ah ≤40Ah ≤40Ah ≤40Ah 16– 16– 16– 16– 18– 18– 18– 18– 20– 20– 20– 20– Z3B220 Z3B220 Z3B220 Control unit S3#1 S3#1 S3#1 S3#1 S3#2 S3#2 S3#2 S3#2 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 16: Mounting Possibilities

    Mounting possibilities In danger management system DMS7000 R1P061 power supply rack delivered as complete wired unit, without batteries On L-section plate of the Z1B050 mounting set E3C021 Z1B050 B2F020 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 17: In Cz10 Fire Detection System Control Unit

    In CZ10 fire detection system control unit 5.3.1 On G1E010 universal bracket Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 18 – position one paire of batteries on YAH00’s, the other is positioned on the Z1B050 base of the control unit housing B2F020 B2F020 E3C021 E3C021 Z1B050 Z1B050 AX1201 AX1201 2x YAH00 AX1201 AX1201 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...
  • Page 19: In Cc60 Gas Warning System Control Unit

    12 13 14 15 16 17 18 19 32 33 34 B2F020 E3C021 Z1B050 32 33 34 35 36 37 38 39 AX1201 AX1201 AX1201 AX1201 In CZ1-02 extinguishing system control unit B2F020 E3C021 Z1B050 AX1201 AX1201 Fire & Security Products e1493d Siemens Building Technologies Group 04.2002...