Safety
Acc. to DIN EN 61010 Part 1
Overvoltage category
Degree of pollution
Fire stability Class
Acc. to UL 94
Insulation tests
EN61010
IEC 255-5: ANSI/IEEE C37.90.0
Voltage test (routine test)
- Auxiliary power to fault relay
- Auxiliary power to RS232 interface
- Fault relay to RS232 interface
Surge voltage test (type test)
61010-1 3rd edition
- Auxiliary power to relay
- Auxiliary power to RS232 interface
- Fault relay to RS232 interface
EMC Tests on interference emission
Standard: EN 50081-1
Conducted interference only power
supply voltage,
CISPR 22, EN 55022
DIN VDE 979 Teil 22
Radio interference field strength
CISPR 11, EN 55011
DIN VDE 0878 Teil 22
Seite 14 von 20
III
2
V0
each
DC 5 kV / 1 s (with bypass capacitors)
AC 3,51 kV/50 Hz/1 s
(without bypass capacitors)
each
6,4 kV (peak);
1,2 µs /50 µs; 0,5 J;
3 pos. und 3 neg. surges in
Intervals of 5 s
All circuits, Class III
(not on open contacts)
150 kHz to 30 MHz
Limit Class A
Limit Class A
30 MHz to 1000 MHz
Limit Class A
Limit Class A