C53000-B1100-C602-1
2.3
Combined specifications
Environmental conditions (operate only in rooms)
Ambient Temperatures
Temperature recommended during the
operation
Temperature during the transport and the
storage
Humidity
mean value per year
Maximum value per year
Condensation during operation
Condensation during transport and
storage
Other environmental indications
Maximum height over sea level
Degree of pollution
Class of protection according to IEC
60529
Overvoltage category
Alarm relay
Relay
Maximum switching voltage (nominal
value):
Maximum switching current
Maximum switching capability
Allowed current for contacts
Fuses
Soldered
Exchangeable
7XV5810 0xA00
-5 °C to +55 °C (23 °F to 131 °F)
-25 °C to +70 °C (-13 °F to 158 °F)
≤ 75 % relative humidity
95 % relative humidity on 30 days per
year
Not allowed
Allowed
2000 m
2
IP 20
III
MSR-Relay, 1 NC (open) contact
Potential free
2-pole connector
AC 240 V
5 A
DC: 50 W at 300 V
DC 270 W at 35 V
AC 2000 VA
5 A
T2.0 A
T1.6 A / AC 250 V / DC 300 V
Operating Instructions
Seite 13 von 20