Table 52: BACnet and MODBUS Points List, continued.
Variable
Analog Values – Read/Write – Commandable, continued.
Return Temp from BMS Used
Return_Temp_from_
when source selection is
BMS
Space 1 CO2 from BMS
Space_1_CO2_from_
Used when source selection
BMS
Space RH from BMS Used
Space_RH_from_
when source selection is
BMS
Space Static from BMS Used
Space_Static_from_
when source selection is
BMS
Space Temp from BMS Used
Space_Temp_from_
when source selection is
BMS
Cooling_Lockout_
Cooling Ambient Lockout
Setpoint
Heating_Lockout_
Heating Ambient Lockout
Setpoint
Preheat_
Preheat Ambient Lockout
Lockout_
Setpoint
Space_Static_
Space Static Pressure Set-
Pressure_Setpoint
Supply_Duct_Static_
Supply Duct Static Pressure
Pressure_
Setpoint
Space_CO2_
Space CO
Setpoint
Exhaust_Fan_CFM_
Exhaust Fan CFM
Setpoint_BMS
SF_Control_Signal_
BMS to control signal for
BMS
supply fan speed
EF_Control_Signal_
BMS to control signal for
BMS
exhaust fan speed
OAD_Control_
Allows the BMS to control
Signal_BMS
Outside_Air_
Outside Air Damper
Damper_Minimum_
Minimum Set-point
Setpoint
Active
Description
Text
set to BMS
is set to BMS
set to BMS
set to BMS
set to BMS
Set-point
Set-point
Set-point
point
Set-point
Set-point
2
Set-point
OAD position
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Inactive Text
Object
Object
Instance
Type
24
AV
25
AV
28
AV
29
AV
30
AV
31
AV
32
AV
33
AV
37
AV
38
AV
39
AV
113
AV
133
AV
134
AV
136
AV
137
AV
CONTROLLER
BACnet and MODBUS Points
BACnet
Access
Hyst
Index
ReadCOV_
0.1
40048
Commandable
ReadCOV_
0.1
40050
Commandable
ReadCOV_
0.1
40056
Commandable
ReadCOV_
0.1
40058
Commandable
ReadCOV_
0.1
40060
Commandable
ReadCOV_
0.1
40062
Commandable
ReadCOV_
0.1
40064
Commandable
ReadCOV_
0.1
40066
Commandable
ReadCOV_
0.1
40074
Commandable
ReadCOV_
0.1
40076
Commandable
ReadCOV_
0.1
40078
Commandable
ReadCOV_
0.1
40080
Commandable
ReadCOV_
0.1
40084
Commandable
ReadCOV_
0.1
40086
Commandable
ReadCOV_
0.1
40090
Commandable
ReadCOV_
1
40092
Commandable
MODBUS
Register
Size
Type
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
Holding
2
93