LG AR-DR11-08A Installation And Operation Manual page 105

Rooftop dedicated outdoor air systems doas 650 to 12,000 cfm
Table of Contents

Advertisement

Table 64: LonTalk Points List.
Access
NV Name
Read-Only Points, continued.
nvo
DigStatus.bit09
nvo
DigStatus.bit10
nvo
DigStatus.bit11
nvo
DigStatus.bit12
nvo
DigStatus.bit13
nvo
DigStatus.bit14
nvo
DigStatus.bit15
nvo
GlobalAlarm
nvo
ActTmpSpt
nvo
CirA_SatDschT
nvo
CirB_SatDschT
nvo
ColdCoil1Temp
nvo
EntWterTempA
nvo
EntWterTempB
nvo
ExhaustTemp
nvo
LeavWterTempA
nvo
LeavWterTempB
nvo
MixedTemp
nvo
OutsideTemp
nvo
SpaceTemp
nvo
SupplyTemp
Write-Only Points
nvi
EconEnthTrig
nvi
ExhCFMSetpt
nvi
OACFMSetpt
nvi
SupCFMSetpt
nvi
DehumSetpt
nvi
OADMinSetpt
nvi
UnocRHSetpt
nvi
SpaceCO2Setpt
nvi
SpacePressSpt
nvi
SupPressSetpt
nvi
OccUnocc
nvi
ResetAlarms
nvi
SystemEnable
nvi
TempDeadband
nvi
EconTempTrig
nvi
IADewptTrig
nvi
TempSetpt
nvi
UnocCoolSetpt
nvi
UnocHeatSetpt
SNVT Type
state.bit09
state.bit10
state.bit11
state.bit12
PreHeat Enable Digital Output
state.bit13
Reversing Valve Digital Output
state.bit14
Damper Status (OAD or RAD indicating a path of
state.bit15
switch (95)
temp_p (105)
Active Temperature Set-point
temp_p (105)
Circuit A Saturated Discharge Temperature
temp_p (105)
Circuit B Saturated Discharge Temperature
temp_p (105)
temp_p (105)
Leaving Water Temperature Circuit A
temp_p (105)
Leaving Water Temperature Circuit B
temp_p (105)
temp_p (105)
Entering Water Temperature Circuit A
temp_p (105)
Entering Water Temperature Circuit B
temp_p (105)
temp_p (105)
temp_p (105)
temp_p (105)
enthalpy (153)
Economizer Enthalpy Enable Se-tpoint
flow_p (161)
Exhaust Fan CFM Set-point
flow_p (161)
flow_p (161)
Supply Fan CFM Set-point
lev_percent (81)
Dehumidification Set-point
lev_percent (81)
Outside Air Damper Minimum Set-point
lev_percent (81)
Unoccupied Dehumidification %RH Set-point
ppm (29)
press_p (113)
Space Static Pressure Set-point
press_p (113)
Supply Duct Static Pressure Set-point
switch (95)
switch (95)
switch (95)
Master system enable/disable point
temp_diff_p
Heat/Cool Spt Deadband (Space or Return control
(147)
temp_p (105)
Economizer Ambient Temp Enable Set-point
temp_p (105)
Inside Dewpoint Dehumidification Set-point
temp_p (105)
Main Temperature Set-point
temp_p (105)
Unoccupied Cooling Set-point
temp_p (105)
Unoccupied Heating Set-point
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Description
Supply Fan Status
Exhaust Fan Status
Heat Wheel Status
Occupied Status
airflow)
General alarm output
Cold Coil Temperature
Exhaust Temperature
Mixed Temperature
Outside Air Temperature
Space Temperature
Supply Temperature
OAD CFM Set-point
Space CO2 Set-point
Occupancy Command
Alarm Reset Command
is active)
CONTROLLER
LonTalk Points
Notes
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Cooling 1=Heating
0=Unoccupied 1=Occupied
0=Closed 1=Open
0=No Alarms 1=Active Alarms
Heating or Cooling Set-point
Allow Econ when OA Enthalpy<Spt
Divide desired CFM by 100.
Divide desired CFM by 100.
Divide desired CFM by 100.
%RH for Space or Return control
0=Occupied 1=Unoccupied
Divided by 2.
Add/subtract to/from the
set-point
Allow Econ when OAT<Spt
Supply, Space, or Return target
105