Lontalk Points - LG AR-DR11-08A Installation And Operation Manual

Rooftop dedicated outdoor air systems doas 650 to 12,000 cfm
Table of Contents

Advertisement

CONTROLLER

LonTalk Points

Table 63: LonTalk Points List.
Access
NV Name
Read-Only Points
nvo
LatestAlm
nvo
UnitStatus
nvo
ExhCFM
nvo
OACFM
nvo
SupCFM
nvo
CoolingRamp1
nvo
CWV1Out
nvo
ElecHeat1Out
nvo
ERecoveryOut
nvo
ExhFan1Out
nvo
HeatingRamp
nvo
HGROut
nvo
HPumpHeatRamp
nvo
HWV1Out
nvo
ModCompOutBMS
nvo
ModFurn1Out
nvo
OADOutput
nvo
OutsideRH
nvo
SpaceRH
nvo
SupFan1Out
nvo
Space1CO2
nvo
SpacePress
nvo
SupDuctPress
nvo
DigAlarms
nvo
DigAlarms.bit00
nvo
DigAlarms.bit01
nvo
DigAlarms.bit02
nvo
DigAlarms.bit03
nvo
DigAlarms.bit04
nvo
DigAlarms.bit05
nvo
DigAlarms.bit06
nvo
DigAlarms.bit07
nvo
DigStatus
nvo
DigStatus.bit00
nvo
DigStatus.bit01
nvo
DigStatus.bit02
nvo
DigStatus.bit03
nvo
DigStatus.bit04
nvo
DigStatus.bit05
nvo
DigStatus.bit06
nvo
DigStatus.bit07
nvo
DigStatus.bit08
104
SNVT Type
count (8)
count (8)
Startup and Operation Information
flow_p (161)
flow_p (161)
flow_p (161)
lev_percent (81)
lev_percent (81)
Chilled Water 1 Valve Analog Output
lev_percent (81)
lev_percent (81)
Energy Recovery Analog Output
lev_percent (81)
Exhaust Fan Speed Analog Output
lev_percent (81)
lev_percent (81)
lev_percent (81)
lev_percent (81)
Hot Water Valve 1 Analog Output
lev_percent (81)
Modulating Compressor Analog Output BMS
lev_percent (81)
Mod Gas Furnace 1 Analog Output
lev_percent (81)
Outside Air Damper Analog Output
lev_percent (81)
lev_percent (81)
lev_percent (81)
Supply Fan Speed Analog Output
ppm (29)
press_p (113)
press_p (113)
state (83)
state.bit00
state.bit01
state.bit02
state.bit03
state.bit04
state.bit05
state.bit06
Outside Filter Alarm (Dirty Filter)
state.bit07
state (83)
state.bit00
Compressor 1 Enable Digital Output
state.bit01
Compressor 2 Enable Digital Output
state.bit02
Compressor 3 Enable Digital Output
state.bit03
Compressor 4 Enable Digital Output
state.bit04
state.bit05
state.bit06
state.bit07
Furnace 1 Stage 1 Digital Output
state.bit08
Furnace 2 Stage 1 Digital Output
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Description
Most recent alarm
Total Exhaust Fan CFM
OAD CFM
Total Supply Fan CFM
Cooling Ramp 1 Status Value
Electric Heater 1 Analog Output
Heating Ramp
Hot Gas Reheat Analog Output
Heat Pump Heating Ramp
Outside % Relative Humidity
Space % Relative Humidity
Space 1 CO
ppm
2
Space Static Pressure
Supply Duct Static Pressure
Digital Alarm States
Circuit A High Pressure Switch
Circuit A Low Pressure Switch
Circuit B High Pressure Switch
Circuit B Low Pressure Switch
Drain Pan Alarm
Freeze Stat Alarm
Shutdown alarm status
Digital Status States
Condenser Fan 1 Digital Output
Condenser Fan 2 Digital Output
Condenser Fan 3 Digital Output
Notes
See Alarms Data Table
See Unit Status Mode Table
Multiply by 100 for CFM.
Multiply by 100 for CFM.
Multiply by 100 for CFM.
Compressor Capacity
Compressor Capacity
16 bit packed
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
0=Normal 1=Alarm
16 bit packed
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On
0=Off 1=On

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents