LG AR-DR11-08A Installation And Operation Manual page 102

Rooftop dedicated outdoor air systems doas 650 to 12,000 cfm
Table of Contents

Advertisement

CONTROLLER
BACnet and MODBUS Points
Table 61: BACnet and MODBUS Points List, continued.
Variable
Binary Values – Read Only, continued.
Al_SuctHiP_COMP.Active
Al_SuctLowP_COMP.Active
High_Ent_Water_Temp_CircA.
Active
High_Ent_Water_Temp_CircB.
Active
Low_Ent_Water_Temp_CircA.
Active
Low_Ent_Water_Temp_CircB.
Active
Return_Water_Temp_2_Alarm.
Active
Supply_Water_Temp_2_Alarm.
Active
Water_Leak_Detector_Alarm.
Active
HP_Defrost_Active.Active
Comp_Staging_Order_
Skipped.Active
Heat_Pump_Heating_Lock_
Out_Alarm. Active
EVD_PrePosition_Alarm.Active
Integer Values – Read Only
Allow_Fan_Delay_Remaining
Supply_Fan_Delay_Remaining
Exhaust_Fan_Delay_
Remaining
LatestAlm
102
Ac-
Description
tive
Text
Compressor Envelope
Alarm Normal
- SuctHiP_COMP
Compressor Envelope
Alarm Normal
- SuctLowP_COMP
High Entering Water
Alarm Normal
Temp Alarm - Circuit A
High Entering Water
Alarm Normal
Temp Alarm - Circuit B
Low Entering Water
Alarm Normal
Temp Alarm - Circuit A
Low Entering Water
Alarm Normal
Temp Alarm - Circuit B
Return Water Temp 2
Alarm Normal
Alarm
Supply Water Temp 2
Alarm Normal
Alarm
Water Leak Detector
Alarm Normal
Alarm
Heat Pump Defrost
Alarm Normal
Alarm
Compressor Staging
Order is Skipped
Alarm Normal
Warning
Heat Pump Heating
Alarm Normal
Locked Out Alarm
Unexpected EEV
Alarm Normal
Position
Startup Sequence Fan
Damper Delay. Time
before enabling Fan
startup sequence.
Supply Fan startup
sequence. Time before
starting supply fan.
Exhaust Fan startup
sequence. Time
before starting exhaust
fan.
Most recent alarm. See
Alarm Table.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Inactive
Object
Object
Text
Instance
Type
618
BV
ReadCOV_NoWrite
619
BV
ReadCOV_NoWrite
620
BV
ReadCOV_NoWrite
621
BV
ReadCOV_NoWrite
623
BV
ReadCOV_NoWrite
624
BV
ReadCOV_NoWrite
626
BV
ReadCOV_NoWrite
627
BV
ReadCOV_NoWrite
628
BV
ReadCOV_NoWrite
631
BV
ReadCOV_NoWrite
632
BV
ReadCOV_NoWrite
633
BV
ReadCOV_NoWrite
634
BV
ReadCOV_NoWrite
1
IV
ReadCOV_NoWrite
2
IV
ReadCOV_NoWrite
3
IV
ReadCOV_NoWrite
7
IV
ReadCOV_NoWrite
MODBUS
Access
Hyst Index
0
10568 Discrete
0
10569 Discrete
0
10570 Discrete
0
10571 Discrete
0
10573 Discrete
0
10574 Discrete
0
10576 Discrete
0
10577 Discrete
0
10578 Discrete
0
10579 Discrete
0
10580 Discrete
0
10581 Discrete
0
10582 Discrete
1
30182
1
30184
1
30186
1
30194
Register
Size
Type
Input
2
Input
2
Input
2
Input
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents