LG AR-DR11-08A Installation And Operation Manual page 101

Rooftop dedicated outdoor air systems doas 650 to 12,000 cfm
Table of Contents

Advertisement

Table 60: BACnet and MODBUS Points List, continued.
Variable
Binary Values – Read Only, continued.
Al_DscgHiP_COMP.Active
Al_DscgHiTemp_COMP.Active
Al_DscgLowP_COMP.Active
Al_EEPROM_EVD_1.Active
Al_EEV_A_EVD_1.Active
Al_EmergencyClosing_EVD_1.
Active
Al_EVD_Offline_EVD_1.Active
Al_FW_CompatibErr_EVD_1.
Active
Al_HiCurr_COMP.Active
Al_HiRatioP_COMP.Active
Al_HiT_Cond_EVD_1.Active
Al_IncompleteClosing_EVD_1.
Active
Al_LOP_A_EVD_1.Active
Al_Low_SH_A_EVD_1.Active
Al_LowDeltaP_COMP.Active
Al_LowRatioP_COMP.Active
Al_LowSuct_A_EVD_1.Active
Al_MOP_A_EVD_1.Active
Al_S1_EVD_1.Active
Al_S2_EVD_1.Active
Al_S4_EVD_1.Active
Active
Description
Text
Compressor Envelope
- High Discharge
Alarm Normal
Pressure Alarm
Compressor Envelope
- High Discharge
Alarm Normal
Temperature Alarm
EVD Low Discharge
Alarm Normal
Pressure Alarm
EVD EEPROM Alarm Alarm Normal
ExV Motor Alarm -
Alarm Normal
Valve A
EVD Emergency
Alarm Normal
Closing Alarm
EVD Offline
Alarm Normal
Communication Alarm
EVD Firmware
Alarm Normal
Compatibility Alarm
Compressor Envelope
Alarm Normal
- High Current Alarm
Compressor Envelope
- High Pressure Ratio
Alarm Normal
Alarm
Al_HiT_Cond_EVD_1 Alarm Normal
EVD Incomplete
Alarm Normal
Closing Alarm
EVD Low Operating
Alarm Normal
Pressure Alarm - Valve A
"EVD Low SuperHeat
Alarm
Alarm Normal
- Circuit A"
Compressor Envelope
- Low Pressure
Alarm Normal
DeltaAlarm
Compressor Envelope
- Low Pressure Ratio
Alarm Normal
Alarm
Low Suction
Refrigerant
Alarm Normal
Temperature - Circuit A
EVD Max Operating
Alarm Normal
Pressure Alarm - Valve A
EVD-S1 Suction
Alarm Normal
Pressure Sensor Alarm
EVD-S2 Suction
Temperature Sensor
Alarm Normal
Alarm
EVD-S4 Discharge
Temperature
Alarm Normal
Sensor Alarm
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Inactive
Object
Object
Text
Instance
Type
591
BV
ReadCOV_NoWrite
592
BV
ReadCOV_NoWrite
593
BV
ReadCOV_NoWrite
594
BV
ReadCOV_NoWrite
595
BV
ReadCOV_NoWrite
597
BV
ReadCOV_NoWrite
598
BV
ReadCOV_NoWrite
599
BV
ReadCOV_NoWrite
600
BV
ReadCOV_NoWrite
601
BV
ReadCOV_NoWrite
602
BV
ReadCOV_NoWrite
603
BV
ReadCOV_NoWrite
604
BV
ReadCOV_NoWrite
606
BV
ReadCOV_NoWrite
608
BV
ReadCOV_NoWrite
609
BV
ReadCOV_NoWrite
610
BV
ReadCOV_NoWrite
612
BV
ReadCOV_NoWrite
614
BV
ReadCOV_NoWrite
615
BV
ReadCOV_NoWrite
617
BV
ReadCOV_NoWrite
CONTROLLER
BACnet and MODBUS Points
Access
Hyst Index
0
10541 Discrete
0
10542 Discrete
0
10543 Discrete
0
10544 Discrete
0
10545 Discrete
0
10547 Discrete
0
10548 Discrete
0
10549 Discrete
0
10550 Discrete
0
10551 Discrete
0
10552 Discrete
0
10553 Discrete
0
10554 Discrete
0
10556 Discrete
0
10558 Discrete
0
10559 Discrete
0
10560 Discrete
0
10662 Discrete
0
10564 Discrete
0
10565 Discrete
0
10567 Discrete
MODBUS
Register
Size
Type
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents