BACnet and MODBUS Points

Table 50: BACnet and MODBUS Points List.
Variable
Analog Inputs – Read Only
Cold_Coil_1_Temp_Analog_
Input
Exhaust_Temp_Analog_Input
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Mixed_Temp_Analog_Input
Outside_Air_Temp_Analog_
Input
Return_Temp_Analog_Input
Leaving_Water_Temp_1_
Analog_Input
Space_Setpoint_Slider_
Analog_Input
Space_Temp_Analog_Input
Supply_Temp_Analog_Input
Entering_Water_Temp_1_
Analog_Input
Outside_RH_Analog_Input
Return_RH_Analog_Input
Space_RH_Analog_Input
Space_Static_Pressure_
Analog_Input
Supply_Duct_Static_
Pressure_Analog_ Input
Space_CO2_1_Analog_Input
Circuit_A_Discharge_
Pressure_Analog_ Input
Circuit_B_Discharge_
Pressure_Analog_ Input
Exhaust_Fan_Speed_
Analog_Input
Supply_Fan_Speed_Analog_
Input
Entering_Water_Temp_2_
Analog_Input
Leaving_Water_Temp_2_
Analog_Input
Active
Description
Text
Cold Coil 1 Temperature
Exhaust Temperature
Controls Lite Cooling
Coil Set-point
Temperature
Controls Lite Supply Set-
point Temperature
Mixed Temperature
Outside Air Temperature
Return Temperature
Leaving Water
Temperature Circuit A
Space Set-point Slider
Analog Input
Space Temperature
Supply Temperature
Entering Water
Temperature Circuit A
Outside % Relative
Humidity
Return % Relative
Humidity
Space % Relative
Humidity
Space Static Pressure
Supply Duct Static
Pressure
Space 1 CO
ppm
2
Circuit A Discharge
Pressure
Circuit B Discharge
Pressure
Exhaust Fan Speed
Remote Command
Analog Input value
Supply Fan Speed
Remote Command
Analog Input value
Entering Water
Temperature Circuit B
Leaving Water
Temperature Circuit B
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Inactive
Object
Object
Text
Instance
Type
25
AI
ReadCOV_NoWrite 0.1
30
AI
ReadCOV_NoWrite 0.1
31
AI
ReadCOV_NoWrite 0.1
32
AI
ReadCOV_NoWrite 0.1
35
AI
ReadCOV_NoWrite 0.1
37
AI
ReadCOV_NoWrite 0.1
41
AI
ReadCOV_NoWrite 0.1
42
AI
ReadCOV_NoWrite 0.1
43
AI
ReadCOV_NoWrite 0.1
44
AI
ReadCOV_NoWrite 0.1
45
AI
ReadCOV_NoWrite 0.1
46
AI
ReadCOV_NoWrite 0.1
86
AI
ReadCOV_NoWrite 0.1
88
AI
ReadCOV_NoWrite 0.1
89
AI
ReadCOV_NoWrite 0.1
94
AI
ReadCOV_NoWrite 0.001 30366
95
AI
ReadCOV_NoWrite 0.01 30368
116
AI
ReadCOV_NoWrite
119
AI
ReadCOV_NoWrite 0.1
121
AI
ReadCOV_NoWrite
143
AI
ReadCOV_NoWrite
155
AI
ReadCOV_NoWrite
161
AI
ReadCOV_NoWrite 0.1
162
AI
ReadCOV_NoWrite 0.1
CONTROLLER
BACnet and MODBUS Points
Access
Hyst Index
30244
30254
30256
30258
30264
30268
30276
30278
30280
30282
30284
30286
30350
30354
30356
10
30402
30408
1
30412
1
30456
1
30462
30468
30470
MODBUS
Register
Size
Type
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
91