TS06A, LPG Anodized Aluminum, Electronic Dispenser Meter Installation, Operation & TS06AS86 with thermo well Parts Manual Non-Compensated With Thermo Well Assembly No., Single __ TS06AS83 __ TS06AS86 Twin __ TS06AS84 __ TS06AS88 for register __ TS06AE83 __ TS06AE86 with EMR³ __ TS06AE93 __ TS06AE96 with ELNC...
This manual provides warnings and procedures that are intended to inform the owner/operator of the hazards present when using the Tuthill Transfer Systems, TUTHILL meters and other products. The reading of these warnings and the avoidance of such hazards is strictly in the hands of the owner/operator of the equipment.
Installation & Operation Installation: In critical installation, block valves and by-pass lines are recommended. This allows the meter to be ser- Before Start-up of the Meter, make certain: viced without interruption of flow in a critical process The meter is properly mounted, secured and piped application.
The meter is not designed to operate on air, but the design stalling pumps. Give particular attention to factors like: use and materials of construction of the TUTHILL meter allows of foot valves, pipe size to the inlet and conformance to net...
Page 6
If the receiving instrument (register) is more than 200’ (60 m) cable distance from the flow meter, an amplifier is required on the pulse signal. If this option was not ordered, please consult with Tuthill prior to start-up. Both pins covered: 5VDC Regulated 1 pin exposed: 5.5 - 12 VDC...
Installation & Operation continued TS06A with SCL & ER9044 (ELNC-1141) register, AC powered through EL2057 ELPS-2057 AC power supply & barrier EL0300-5 SCL inside flow meter front cover This drawing does not guarantee compliance for intrinsically safe apparatus. Refer to CD1000, CD1001 and State &...
Page 8
Installation & Operation continued TS06A with SCL & ER-9044-2 (ELNC-1141E) register, with Backlight Display & 10:1 Pulse, AC powered through EL2057 This drawing does not guarantee compliance for intrinsically safe apparatus. Refer to CD1000, CD1001 and- State & National electrical codes. Cable lengths are limited by entity parameters.
Page 9
Installation & Operation continued Theory of Operation; pass lines. The TUTHILL meters LPG metering system combines an When properly installed, this line must permit free flow in oval gear positive displacement meter, differential valve, either direction. If the vent line is closed the meter will not strainer and vapor eliminator in one assembly.
Page 10
Service Depart- ment at TUTHILL meters for assistance if this occurs. As product is bleeding from the bleed valve, slowly reo- pen and close the valve/nozzle on the discharge line.
Page 12
Flow Meter Maintenance Danger!! Danger!! Danger!! Relieve all internal pressure before servicing. Line pressure must be 0.0 PSI Serious injury or death form fire or explosion could result from maintenance of an Meter Disassembly: Install a new oval gear set (17) if necessary. Gears If your meter is equipped with an electronic register, should be perpendicular to each other.
Flow Meter Maintenance Inlet Check Valve Service: (Optional component) Inspect the slide valve. Remove and build–up of salts or Disconnect the outlet piping from the meter assembly at dirt which may cause the valve to stick. The valve the differential valve outlet flange.
Page 14
Flow Meter Maintenance 3/4” Back Check Valve Assembly (Optional) Item # Qty Description Part # 1 Complete Backcheck Valve Assy. VP3075 1 Piston, 3/4" Backcheck Valve MP4001 1 Spring MS8031 1 "O" Ring SL3114-UL 1 Body, 3/4" Backcheck Valve MP3075-1 1 Poppet, 3/4"...
Parts List SINGLE TWIN Item # Description Relief Valve MS8400 MS8400 Flange 1" FNPT (ALUM) MP2568 MP2568 Flange 1" FBSP (ALUM) MP2569 MP2569 1/4-20 x 5" Hex Bolt FS2910 FS2910 Cover, Vapor Eliminator MP2561 MP2561 Housing, Vapor Eliminator MP2565 MP2565 O-Ring, Buna SL3156 SL3156...
Page 17
Trouble Shooting Problem Probable Cause and Solution Leakage from seal cover. Seal has been damaged due to shock Cover bolts have not bee tightened sufficiently Replace seal and /or re-torque bolts Product flows through meter but the regis- ...
Page 18
The SCL may be LINEARIZER MODE: used in conjunction with other Tuthill electronics to solve If a metering device is not producing an output within the many of your electronic interface requirements.
Page 19
Flow Meter Calibration METER CALIBRATION: Finally: Flow meter re-calibration should be on a volume Re-seal the flow meter. equal to 1 minute of flow at maximum flow rate. Enter date and % correction on the permanent flow ...