3.2.1.2.Core identification in open circuit and continuity
to S1 Transmitter mode
Mode usable in all cases.
Connect the red probes to the receiver, press the «
measurement » button, the "Open circuit identification
and S1 continuity" LED illuminates.
The cable being cut, probe any 2 cores of the 3.
Press the « measurement » button, the « end of
measurement » LED turns off.
Wait for the result (3 seconds), the « end of measurement »
LED turns on.
The result will depend on the probed cores and on the
cable extremity they are connected to :
If the probe is connected towards S1, the LED "YES"
If the phase is identified, the L1, L2 or L3 LED
Repeat the operation to identify the other cores.
The receiver designates the free conductor.
IMPLEMENTATION
for the S1 continuity turns on.
illuminates.
22 / 30