When installing Air Guide Duct
• Check and make sure that screws do not damage the copper pipe.
• Secure air guide duct on guard fan,

Selecting A Location In Cold Climates

Outdoor Unit
Anchor Bolt
When operating the unit in a low outdoor ambient temperature, be sure to fol-
low the instructions described below.
To prevent exposure to wind, install the unit with its suction side facing the wall.
Never install the unit at a site where the suction side may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of the unit.
In heavy snowfall areas it is very important to select an installation site where the snow will
not affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is not
affected by the snow (If necessary construct a lateral canopy).
1. Construct a large canopy.
2. Construct a pedestal. Install the unit high
enough off the ground to prevent it being buried
under snow.
Outdoor Unit
Support
Base Surface
Soft rubber designed to cut off
vibration from rack to wall.
(not supplied with product)
Heat Pump Installation Guide
Designed to cut off
residual vibration
from outdoor unit to
rack. (not supplied
with product)