www.mgeups.com
4.2.4.3 Programmable outlet 2
UM-Client
Outlet 2
During backup time, Shutdown Timer of UM-Client is reached: after a period of backup time
defined by the user (UM-Editor, UM-Console +), the server hosting UM-Client is shut down
(caution, automatic restart of the server when utility is restored is not guaranteed in this situation)
During normal operation, sending of a UPS shutdown command to the SNMP agent by the user
(UM-Console+, UM-Vision). Shutdown of all servers and possibility of UPS shutdown (depending
on its configuration) after the Shutdown Duration of the SNMP agent.
During normal operation, sending of a reboot command to the UPS (toggle) by the user.
Shutdown of all servers and possibility of UPS shutdown (depending on its configuration) after the
Shutdown Duration of the SNMP agent and rebooting of the whole system after a time delay
defined by the user (UM-Console).
During normal operation , user-defined On / Off cycle, shutdown of all servers and possibility of
UPS shutdown (depending on its configuration) after the Shutdown Duration of the SNMP agent
and reboot of the entire system at the time defined by the user ( Web Interface, UM-Vision, UM-
Console +),
Consult the Appendix section to view the chronograms of these sequences.
T H E
U N I N T E R R U P T I B L E
Network Management Cards – User Manual
Trap 29
ShutoffTimer.2
Trap 31 Shutd'n
Duratio
n.2
Trap 32
Shutd'n
P O W E R
34003676EN/AA
Restart
Delay.2
P R O V I D E R
Rebo
ot