MGE UPS Systems 66102 User Manual

MGE UPS Systems 66102 User Manual

Network management card
Hide thumbs Also See for 66102:
Table of Contents

Advertisement

www.mgeops.com
ENERGIZE YOUR ENTERPRISE
Network Management Card
– User Manual
Network

Management Card

(66102 & 66103)
User manual
34003991EN/DA
Page
1/120

Advertisement

Table of Contents
loading

Summary of Contents for MGE UPS Systems 66102

  • Page 1: Management Card

    ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Network Management Card (66102 & 66103) User manual 34003991EN/DA Page 1/120...
  • Page 2: Table Of Contents

    Contents MGE OFFICE PROTECTION SYSTEMS NETWORK SOLUTION ENERAL RESENTATION 1.1.1 Connecting the UPS to the Ethernet network 1.1.2 Protection of the computers/servers 1.1.3 Supervision of the UPSs over the network 1.1.4 Connection RESENTATION OF THE ETWORK 1.2.1 Compatibility with UPSs 1.2.2 Direct sending of E-mail 1.2.3...
  • Page 3 4.3.1 Email Notification 4.3.2 E-mail Message Settings ONFIGURATION 4.4.1 Network settings 4.4.2 System 4.4.3 Notified Applications 4.4.4 Central shutdown configuration 4.4.5 Access control 4.4.6 Date and time 4.4.7 Firmware upload NVIRONMENT ENSOR OPTION 4.5.1 Characteristics 4.5.2 Environment Status 4.5.3 Environment Settings 4.5.4 SERVER PROTECTION UP OF THE SHUTDOWN PARAMETERS...
  • Page 4 JBUS TABLE 7.4.1 Data for Pulsar 700 / 1000 / 1500 7.4.2 Data for Pulsar M 2200 / 3000 7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 7.4.4 Data for Pulsar MX frame 15 / 20 7.4.5 Sensor data 7.4.6 Other data APPENDICES...
  • Page 5: Mge Office Protection Systems Network Solution

    1 MGE Office Protection Systems Network Solution 1.1 General Presentation MGE Office Protection Systems Network Solution: provides information on events concerning the supply of power to the computers connected to your computer network, carries out automatic shutdown of computer systems, monitors and controls all the UPSs connected to the network.
  • Page 6: Connecting The Ups To The Ethernet Network

    1.1.1 Connecting the UPS to the Ethernet network This function can be performed either through network Cards inserted in the UPS (Network Management Card) or through a software "agent" running on a nearby PC that is called the Network Management Proxy. The Network Management Card or Proxy: - manages communication with the UPS (as well as local protection of the machine on which Proxy is installed) - periodically accesses the information concerning the UPS...
  • Page 7: Supervision Of The Upss Over The Network

    1.1.3 Supervision of the UPSs over the network Depending on your needs, you can either use: Your Internet browser to monitor each UPS, as Management Proxy and Management Card includes a Web server Your company’s standard Network Management System (HP-Openview, CA Unicenter, HP Insight Manager, IBM Tivoli Netview) To simplify integration of MGE Office Protection Systems UPSs, you can use one of the Network Management System Kits for MGE devices.
  • Page 8: Presentation Of The Network Management Card (Nmc)

    Note: If the UPS's NT is below that indicated in the table above, contact MGE's Office Protection Systems technical support. The Network Management Card (66102) is not compatible with Pulsar EX 7/10, Pulsar EX 15/20/30, Pulsar ESV+, 8/11/14/22 ranges. Network Management Cards acquire information on the operation status of the UPS systems and provide remote control of these systems by means of an ETHERNET network from any SNMP administration station or Web browser.
  • Page 9: Direct Sending Of E-Mail

    Network Management Cards are compatible with the "Enterprise Power Management" supervision system and with the MGE Office Protection Systems network protection system. Network Shutdown Module Entreprise Power Manager Management-Pac 2 1.2.2 Direct sending of E-mail When a UPS event occurs, the Network Management Card can directly notify up to 4 intranet or extranet addresses by e-mail.
  • Page 10: Technical Data

    1.3 Technical data 1.3.1 Hardware characteristics Dimensions Dimensions (L x l x H) 132 x 66 x 42 mm Weight (gr) 70 g Storage Storage temperature -10 ° C to 70 ° C Ambient conditions Operating temperature 0 ° C to 40 ° C Ambient humidity 90 % RH max without condensation ROHS...
  • Page 11: Administration

    1.3.4 Administration Up to 50 workstations protected by Network Shutdown Modules - Central or local configuration. Up to 5 browsers connected at the same time (3 in SSL). Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 E-mail sending configurable according to UPS alarms and transmission of a periodical report.
  • Page 12: Mib (Management Information Base)

    Recording of events and measurements in the card log Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a dry contact Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m) Hot installation 1.3.7 MIB (Management Information Base) Compatible with MIB MGE Office Protection Systems V1.7...
  • Page 13: Default Parameters

    1.3.8 Default parameters Function Parameter Network IP address Subnet mask Gateway Address BOOTP/DHCP Firmware Upload SMTP server System UPS Contact UPS Location History log interval (sec.) Environment log interval (sec.) Default Language Manager table Access control User name Password Community name read Trap port Date and time Date and time adjustment...
  • Page 14: Installation

    2 Installation 2.1 Unpacking and check on contents The installation kit contents: A Network Management Card (66102) A serial communication cable for configuration (34003918) Installation manual (34003905) 2.2 Indications ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA MAC address...
  • Page 15: Installation In The Ups

    Flashing 2.3 Installation in the UPS The Network Management Card (66102) can be "hot" installed in all UPSs of the MGE Office Protection Systems range equipped with a Minislot without having to shut it down. Remove the protective plastic cover from the Minislot...
  • Page 16: Sensor Installation (Option)

    2.4 Sensor installation (option) The Environment sensor is available as an option on the Network Management Card and is available from MGE Office Protection Systems (reference 66846). The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity, status of two external contacts.
  • Page 17: Configuration

    Stop bits: 1 Flow control: none "Locally reproduce the characters entered" option: deactivated. Enter MGEUPS or mgeups. The main menu is displayed: ----------------------------------------------------------------------------- MGE UPS SYSTEMS NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration 3 : Set Login Password to Default...
  • Page 18: Your Network Is Equipped With A Dhcp Server

    3.1.1 Your network is equipped with a DHCP server The card is configured by default with this service activated. The card automatically collects IP parameters. To know the IP parameters, type 2, the next menu is displayed: ----------------------------------------------------------------------------- Network settings ----------------------------------------------------------------------------- 1 : Read Network settings 2 : Modify Network settings...
  • Page 19: Your Network Is Not Equipped With A Dhcp Server

    3.1.2 Your network is not equipped with a DHCP server In the main menu enter 2, then 2 again. The menu is displayed: Follow the instructions and enter the static IP parameters. At the end of the menu, wait for the "Done" message to be displayed indicating that the IP parameters have been saved.
  • Page 20: Supervision And Administration By Browser

    4 Supervision and administration by browser On a computer equipped with a Web browser (Internet Explorer, FireFox or Netscape recommended), enter the address initialised previously in the Installation chapter (e.g. http://172.17.16.16.) The "UPS properties" home page is displayed. 4.1 Optimising the performance of your browser To view status changes on the UPS in real time, the browser must be configured so that it automatically refreshes all the objects on the current page.
  • Page 21: Ups

    4.2 UPS 4.2.1 UPS properties page This page is automatically refreshed every 10 seconds. From this page, access to the main UPS information is available thanks to the combo box (see screen copy below). The different choices are the following ones: “UPS Status”: (chosen by default) this page gives instant access to the essential information about your UPS.
  • Page 22 4.2.1.1 "UPS" zone: general information on the UPS. Indication of the picture and generic name of the UPS range Computer room: Customised name of your system. You can change this name on the "System" UPS status icon : The various icons showing the status of the UPS are: Normal operation Alarm present.
  • Page 23 UPS without automatic bypass Note: In case of loss of communication with the UPS, all the elements of the synoptic are grey. The various elements of the synoptic are the following ones: AC Normal Input : In tolerances Out of tolerances AC Normal Flow : AC to DC converter powered by AC Normal AC to DC converter not powered by AC...
  • Page 24 Battery : Remaining capacity > 50% Remaining capacity < 50% Battery to be checked (battery test result) Battery Output Flow : DC to AC converter powered by battery DC to AC converter not powered by battery DC to AC Converter Input flow : Energy flow present No energy flow...
  • Page 25 AC Automatic Bypass Flow : Energy flow present No energy flow AC Automatic Bypass Status : Powered Not powered Internal failure AC Manual Bypass Flow : Energy flow present No energy flow AC Manual Bypass Status : Open Closed AC Output Flow : Energy flow present No energy flow...
  • Page 26 UPS measurements : Boxes showing measurements appear when synoptic elements are hovered by the pointer. See example below. These measurements are available for AC to DC converter, Battery, DC to AC converter and automatic bypass. The measurements available in these boxes depend on the UPS range. ENERGIZE YOUR ENTERPRISE Network Management Card –...
  • Page 27 4.2.1.2 "UPS status" zone: Essential information "Active sources": (available on parallel or modular UPS) x UPS + y UPS redundant : x indicates the minimal number of UPS necessary to power the load, y indicates the number of UPS in redundancy. An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold.
  • Page 28 4.2.1.3 Viewing the modules Click on "UPS Modules" scroll list to view the information about the UPS modules. Active sources: x UPS + y UPS redundant : x indicates the minimal number of UPS necessary to power the load, y indicates the number of UPS in redundancy. The addition of these 2 values is the total number of available UPS.
  • Page 29 The Status can take the next forms: when the module is working properly with no alarm. when the module has at least one alarm (level Warning) active. when the module has at least one alarm (level Critical) active. when the module has a communication fault. When the module is working properly with no alarms, the icon is not reactive, otherwise it is reactive and clicking on it makes the page Alarm Table appear.
  • Page 30 4.2.1.4 Viewing the alarms Click on "Alarm Table" scroll list to view the list of current alarms. The table of managed alarms is included in the appendix. The level of the alarms appears like below: Critical Warning Unknown Alarm table for standard UPS ENERGIZE YOUR ENTERPRISE Network Management Card –...
  • Page 31 Alarm table for modular UPS ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 31/120...
  • Page 32 4.2.1.5 Viewing the “About your UPS” window Click on "About your UPS" scroll list to view the information about the UPS and the card. ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 32/120...
  • Page 33: On-Line Help

    4.2.2 On-line help On-line contextual help in English is available at the top of each page by clicking on the Help link, which is always located on the top right corner. The navigation menu of the on-line help is identical to that of the card's pages. The Help page always opens a new window.
  • Page 34: Ups Control

    4.2.3 UPS control Click on the "UPS Control" section in the menu The parameters of this menu can only be modified after entering the "Login" and "Password". The following screen is proposed automatically: The default login and password are: MGEUPS Each field accepts up to 10 characters max.
  • Page 35 UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user manual for more information. This page enables triggering of startup and shutdown sequences The status of each output is displayed by a symbol associated with the Off label (red symbol) or On (green symbol).
  • Page 36 "Immediate On": A sequence to switch on output power is launched immediately. The output is re-powered and the systems supplied start up correctly. "Delayed, safe power down": This is the same switch off sequence as for the "Safe power down" command, but postponed by the number of seconds programmed in the "Off Delay"...
  • Page 37: Ups Weekly Schedule Programming

    4.2.4 UPS weekly schedule programming Click on the "Weekly schedule" section of the menu. UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user manual for more information. The weekly schedule enables the administrator to optimise power consumption or program a reboot of the protected equipment at a set time.
  • Page 38: Shutdown Parameters

    4.2.5 Shutdown parameters This page enables viewing and configuration of UPS operating parameters in battery mode and for power restoration. Click on the "Shutdown parameters" section in the menu to see the list of parameters. When you tick the Show advanced parameters option, extra parameters are displayed. These parameters enable, in particular, adjustment of certain thresholds related to the percentage of remaining battery charge level.
  • Page 39 For the main outlet ("Master" by default) The first shutdown criteria initiates the restart of the If remaining time is under (0 to 99999 seconds, 180 by default) is the minimum remaining backup time from which the shutdown sequence is launched. If battery capacity is under (0 to 100%);...
  • Page 40: Measurements

    4.2.6 Measurements Click on "Measurements" in the menu The next window shows the measurements for a mono phases UPS. The following measurements are saved and time-stamped (env. 430): "AC Normal : Voltage": Value of the utility voltage supplying the UPS "AC Normal : Frequency": Value of the utility frequency supplying the UPS "AC Output : Voltage": Value of the output voltage of your UPS "AC Output : Frequency": Value of the output frequency of your UPS...
  • Page 41: Event Log

    4.2.7 Event log Click on "Event Log". in the menu "Save log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type spreadsheets) "Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this action.
  • Page 42: System Log

    4.2.8 System log Click on "System log". in the menu "Save log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type spreadsheets) "Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this action.
  • Page 43: Notification

    4.3 Notification 4.3.1 Email Notification The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobile telephone transfer systems using text messages (SMS). ENERGIZE YOUR ENTERPRISE Network Management Card –...
  • Page 44 Recipient List: On the left side of this page, up to four recipients can be configured to receive e-mails from the card. Each addressee has its own trigger events, selected from the right side of the page, for which an e-mail is sent. The card’s log indicates e-mail transmission errors.
  • Page 45: E-Mail Message Settings

    4.3.2 E-mail Message Settings This page enables customisation of the content of the messages received by recipients of e-mails sent by the card. Customisation is common to the four recipients that can be notified (see Sender (59 characters maximum) identifies the source of the message. The default value is ups@domain.com. This field is free.
  • Page 46 The body of the e-mail sent is composed of: - Message text, which is free text. - The date and time of the event, as saved in the log. - URL of the card, enabling a direct link with the card to be established. - Attachments, as configured for the e-mail recipients .- duplication of the subject, as configured.
  • Page 47: Configuration

    4.4 Configuration The parameters of this menu can only be modified after entering the "Login" and "Password". The following screen is proposed automatically: The default login and password are: MGEUPS Each field accepts up to 10 characters max. After the login and password are entered, they remain active for 5 minutes. If the browser is closed, they will have to be re-entered.
  • Page 48: Network Settings

    4.4.1 Network settings Click on "Network" in the menu. This menu enables the administrator to configure the network parameters of the card and authorisation of the remote upgrade of the embedded system. IP Address: The IP address of the card (e.g.: 172.17.22.252). Subnet Mask: The mask of the sub-network of your network (e.g.: 255.255.255.0).
  • Page 49 parameters. If no response is received from the server, the card boots with the last saved parameters from the previous start. These parameters are those shown on the page. The default value for this parameter is "Enable" Note 1: If the hostname is not used, the IP address supplied by the DHCP server must be fixed to maintain connection with the clients installed on the stations to be protected.
  • Page 50: System

    4.4.2 System Click on "System" in the menu. This menu enables the customisation of the information on the UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for UPS administration at IT network level and/or electrical maintenance. This field does not appear on any other Web page. By default, its value is "Computer Room Manager".
  • Page 51 Factory Reset button: enables restoration of the default configuration of all the card’s parameters. TCP/IP parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the "Keep TCP/IP parameters" option is selected. Security of this operation is ensured by requesting Login and Password. The default login and password are: MGEUPS Export settings to file: Enables exportation ("Download"...
  • Page 52: Notified Applications

    4.4.3 Notified Applications Click on "Notified Applications" in the menu. Security: The administrator has to enter his/her login/password in order to view this information. This menu enables: The addition of the supervision stations receiving traps and configuration of the trap type. To list all the Notified Applications and the main parameters.
  • Page 53 Output: number of the UPS output from which the client is powered. Configuration: shows where the parameters of the Network Shutdown Module come from: Local (coming from the application) or Central (coming from the card). Central shutdown configuration is available by clicking on the Configuration link. Shutdown duration: the shutdown duration necessary to properly shutdown the computer.
  • Page 54: Central Shutdown Configuration

    4.4.4 Central shutdown configuration Click on "Notified Applications" in the menu, then "Configuration". This page is used to define either the "shutdown" or the "notification" settings used by the Network Shutdown Modules that connect to Network Management Card. These settings are used by the Network Shutdown Modules if they are in central-configuration mode or if their configuration is not valid.
  • Page 55: Access Control

    4.4.5 Access control Click on "Access Control" in the menu. To access this page, the login and password are systematically requested if they have not already been entered. This menu enables configuration of the different parameters enabling secure access to the card via a browser or SNMP.
  • Page 56 SSL Access: When selected, access to the Web interface is made in secure mode (https). Connections with Network Shutdown Modules stay in standard mode (secure TCP) SSL Security Implementation: version 3.0 version 1.0 Method TLS_RSA_WITH_512_MD5 Auth Key Exchange Encryption RC4_512 Digest Changes take effect after a card reboot ENERGIZE YOUR ENTERPRISE...
  • Page 57: Date And Time

    4.4.6 Date and time Click on "Date and Time" in the menu. This menu enables initialisation of the date and time of the card in three different ways. The date format is always of year/month/day type Set manually: Enables initialisation of the date and time of the card, with the values entered in the Date and Time fields.
  • Page 58 Synchronize with NTP server: Enables connection with a time server, either available on the company’s internal network or on the Web. This server communicates GMT time. The IP address or hostname of the time server must be entered, and the time zone of your geographic area must then be selected from the list. Connection is made with the server and the date and time are set after clicking on the "Save"...
  • Page 59: Firmware Upload

    4.4.7 Firmware upload Click on "Firmware Upload" in the menu. This menu enables a new firmware version to be uploaded To upload a new version of the card's firmware, select the file to be loaded using the "Browse…" button and click Upload.
  • Page 60: Environment Sensor (Option)

    4.5 Environment Sensor (option) The environment sensor (66846) is an option that enables temperature and humidity to be measured, and indication of the position of two external contacts. It is connected with a standard network cable to the Card Settings port of the Network Management Card.
  • Page 61: Environment Status

    4.5.2 Environment Status For both measurements, a graduated gauge proposes the following functions: The cursor indicates the current value. Two red zones to the left and right represent the high and low thresholds that can be set on the Environment Settings page.
  • Page 62: Environment Settings

    4.5.3 Environment Settings The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door, alarms or generator unit). The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the protected system.
  • Page 63 Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. The default value is The high alarm disappears when the value drops below the High threshold - Hysteresis value The low alarm disappears when the value returns above the Low threshold + Hysteresis value Input #1 and Input #2: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning, generator unit, etc.).
  • Page 64: Log

    4.5.4 Log The two environment sensor measurements: Temperature and Humidity are recorded at an interval defined by the Environment log interval in the System settings page. By default, this period is 300 seconds. Each measurement is dated and stored in the log of the UPS’s communication card. The size of log files is limited by a time indexing system.
  • Page 65: Server Protection

    Server protection 5.1 Set-up of the shutdown parameters The Network Shutdown Module, on protected server boot, subscribes itself automatically to and sends its essential data: IP Address or hostname of the server on which it is installed: So that the card can inform it of power events. Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up"...
  • Page 66 Utility failure Battery capacity 100% Shutdown if remainig capacity under 5.1.1.1 Backup time before initiating the shutdown procedure (Shutdown After – Shutdown Timer) When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.
  • Page 67: Shutdown Duration

    5.1.1.3 Shutdown when backup time is less than When the Network Management Card detects that the percentage of backup time remaining is less than the value set, the shutdown sequence is started. 5.1.1.4 Shutdown duration Duration (in seconds) required for the system protected by the Shutdown Modules to shut down. The Network Shutdown Modules transmit their own "Shutdown duration"...
  • Page 68: Controlled Outlets

    5.1.2 Controlled outlets Certain UPS models are equipped with controlled outlets (generally 2) which are always dependant on the UPS's main outlet. Shutdown of the main outlet systematically causes shutdown of the programmable outlets. The following notations are used to identify these outlets: Main outlet: Main Controlled outlet 1...
  • Page 69: The Different Server And Ups Shutdown Sequences

    5.1.3.2 Sequential startup It is possible to delay outlet power-on to reduce inrush currents on startup or to sequence the startup of several devices. Controlled outlet startup after a given time is based on startup of the main outlet. 5.2 The different server and UPS shutdown sequences 5.2.1 Extended power outage, shutdown initiated by the Shutdown Timer (Shutdown after) During battery backup time, the Shutdown Timer of the Network Management Card is reached: After a user-defined...
  • Page 70: Case Of Power Restoration Before The End Of The "Shutdown Duration" Counter

    Start shutdown Utility failure output 1 Utility Main output NSM 1 on main output Output 1 NSM 2 on output 1 5.2.3 Case of power restoration before the end of the "shutdown duration" counter If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for a time equal to the forced reboot delay (10 seconds) Start shutdown Utility failure...
  • Page 71: Shutdown Management With 2 Nmc Boards

    5.3 Shutdown management with 2 NMC boards Certain UPS can have 2 NMC boards in order to: Increase the number of protected servers, Protect 2 groups of server connected to different networks physically separated. 5.3.1 Shutdown Duration As described in the 5.1.1.4 paragraph, The Network Shutdown Modules transmit their own "Shutdown duration" to the Network Management Card.
  • Page 72: Configuration Via Rs232

    8 bits, no parity, 1 stop bit, and without flow control. Check that UPS power is on. Enter the MGEUPS or mgeups password (non modifiable). The menu is in English only. ----------------------------------------------------------------------------- MGE UPS SYSTEMS NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration...
  • Page 73: Choice 1: Restart / Reset

    6.1 Choice 1: Restart / Reset Use this function to restart the card; two choices are possible 1 : Hardware Reset: Equivalent to a restart of the electrical power supply. 2 : Restart application: Restarts only the application part. ----------------------------------------------------------------------------- Reset ----------------------------------------------------------------------------- 1 : Hardware Reset...
  • Page 74: Choice 2: Modify Network Settings

    6.2.2 Choice 2: Modify Network settings Enables the modification of network parameters For each of the following questions, you can press <Return> to select the value shown in braces, or you can enter a new value. Should this target obtain IP settings from the network?[N] Static IP address [172.17.18.129]? Subnet Mask IP address [255.255.248.0]? Gateway address IP address [172.17.17.1]?
  • Page 75: Choice 3: Lost Password / Set Login Password To Default

    6.3 Choice 3: Lost password / Set Login Password to Default In the even the login or password is lost, choice 3 enables the return to the default password: ----------------------------------------------------------------------------- MGE UPS SYSTEMS NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset...
  • Page 76: Choice 4: Return To Default Configuration

    6.4 Choice 4: Return to Default Configuration Enables restoration of the default configuration ----------------------------------------------------------------------------- MGE UPS SYSTEMS NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration 3 : Set Login Password to Default 4 : Return to Default Configuration...
  • Page 77: Industrial Network Management Card (Inmc Option)

    7 Industrial Network Management Card (INMC option) 7.1 Presentation 7.1.1 Overview 7.1.2 Functions The Industrial Network Management Card (INMC) provides the same functions than the NMC card described in the previous section of this document. The adding function consists to provide UPS (Uninterruptible Power Supply) data (states and measures) to be sent a computer system.
  • Page 78: Technical Characteristics

    7.1.3 Technical characteristics Functions Parameters JBUS/MODBUS - Baud rate communication - Parity - Slave number RS232 link - Link connection in transmit data (Tx) or receive data (Rx) RS485 link - Termination ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Default values Possible values - 9600 bauds...
  • Page 79: Installation

    7.2 Installation 7.2.1 RS232 link configuration and connection Set the SA2 switches like below: The next figure shows the details of the connection in RS232 mode: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Pin number Function Received data (input) Not connected Transmitted data (output) Not connected...
  • Page 80: Rs485 Link Configuration And Connection

    7.2.2 RS485 link configuration and connection 7.2.2.1 RS485 connection La liaison EIA RS485, en 2 fils ou en 4 fils, doit être polarisée en un point unique de la ligne et adaptée aux deux extrémités de cette ligne pour un fonctionnement correct Normally, the master of the network sets the polarity of the line.
  • Page 81 The settings of the RS485 link are made through the SA1 switches: SA1 description: 1: reserved 2: reserved 3: link termination between T- to R- (2 wires configuration) if set to ON 4: connection T- to R- (2 wires configuration) if set to ON 5: connection T+ to R+ (2 wires configuration) if set to ON 6: reserved 7: reserved...
  • Page 82 7.2.2.2 RS485 link configuration for 2 wires connexion Set the SA2 switches like below to set the RS485 mode: Set the SA1 switches to select the two wires configuration with no termination: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 82/120...
  • Page 83 Set the SA1 switches to select the two wires configuration with termination: The next figure gives a typical bus structure in the two wires configuration: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 83/120...
  • Page 84 7.2.2.3 RS485 link configuration for 4 wires connexion Set the SA2 switches like below: Set the SA1 switches to select the four wires configuration with no termination: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 84/120...
  • Page 85 Set the SA1 switches to select the four wires configuration with termination: The next figure gives a typical bus structure in the four wires configuration: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 85/120...
  • Page 86: Configuration Of The Jbus/Modbus Communication Parameters

    7.2.3 Configuration of the JBUS/MODBUS communication parameters Connect the RS232 link to a terminal (Microsoft Hyper terminal) Use the cord supplied with the card. Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop bit, and without flow control.
  • Page 87 The next menu appears: ----------------------------------------------------------------------------- MGE UPS SYSTEMS NETWORK MANAGEMENT CARD ----------------------------------------------------------------------------- 1 : Reset 2 : Network configuration 3 : Set Login Password to Default 4 : Return to Default Configuration 5 : Jbus configuration 6 : Sensor configuration...
  • Page 88 Setting Jbus configuration : Set Slave number : 0x7 Set the Baud Rate [1: 38400, 2: 19200, 3: 9600, 4: 4800, 5: 2400, 6: 1200] :3 Set data format [1: 8 bits, 2: 7 bits] :1 Set stop bit [1: 1 bits, 2: 2 bits] :1 Set Parity [1: None, 2: Even, 3: Odd] :1 Wait during the new setting is saved ...
  • Page 89 7.2.3.6 Choice 6: Display Jbus frames Enables the display of the Jbus frames: Recv : 01 01 00 00 00 64 3d e1 Send : 01 81 02 c1 91 Recv : 01 03 00 62 00 64 e5 ff Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ...
  • Page 90: Additional Web

    7.3 Additional Web pages The INMC card Jbus parameters could be set through the next page: ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 90/120...
  • Page 91: Jbus Table

    7.4 JBUS table 7.4.1 Data for Pulsar 700 / 1000 / 1500 7.4.1.1 Status table Status description Load protected UPS coupled Unit general alarm UPS in backup Battery low warning Low battery Operation on static switch Communication fault UPS overload Emergency stop Battery to be checked Device ventilation fault...
  • Page 92 7.4.1.2 Measurements table Description of the physical quantity I output U output U battery Output active power Output apparent power % output load level Power factor (Cos PHI) Mains 1 frequency Output frequency Battery backup time Battery charging level U mains 1 Nominal voltage of battery element ENERGIZE YOUR ENTERPRISE Network Management Card...
  • Page 93: Data For Pulsar M 2200 / 3000

    7.4.2 Data for Pulsar M 2200 / 3000 7.4.2.1 Status table Status description Load protected UPS coupled Unit general alarm UPS in backup Battery low warning Low battery Operation on static switch Communication fault UPS overload Emergency stop Battery to be checked Device ventilation fault Manual bypass switch (Q3BP) Battery present...
  • Page 94 7.4.2.2 Measurements table Description of the physical quantity I mains 2 I output U mains 2 U output U battery Output active power Output apparent power % output load level Power factor x 100 Mains 1 frequency Output frequency Battery backup time Battery charging level U mains 1 Nominal voltage of battery element...
  • Page 95: Data For Pulsar Mx 4000 / 5000 / 10000

    7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 7.4.3.1 Status table Status description Load protected UPS coupled Unit general alarm UPS in backup Battery low warning Low battery Operation on static switch Communication fault UPS overload Emergency stop Battery to be checked Device ventilation fault Manual bypass switch (Q3BP)
  • Page 96 7.4.3.2 Measurements table Description of the physical quantity I mains 1 I mains 2 I output I battery U mains 2 U output U battery Output active power Output apparent power % output load level Power factor (Cos PHI) Mains 1 frequency Mains 2 frequency Output frequency Battery backup time...
  • Page 97: Data For Pulsar Mx Frame

    7.4.4 Data for Pulsar MX frame 15 / 20 7.4.4.1 Status table Status description Load protected UPS coupled Unit general alarm UPS in backup Battery low warning Low battery Operation on static switch Communication fault UPS overload Emergency stop Battery to be checked Device ventilation fault Manual bypass switch (Q3BP) Battery present...
  • Page 98 7.4.4.2 Modular fault table Description du Status Module 1 General alarm Fan failure Internal communication fault Inverter thermal overload Inverter fault Inverter fuse blown Load short circuit Module 2 General alarm Fan failure Internal communication fault Inverter thermal overload Inverter fault Inverter fuse blown Load short circuit Module 3...
  • Page 99 Description du Status Module 5 General alarm Fan failure Internal communication fault Inverter thermal overload Inverter fault Inverter fuse blown Load short circuit Module 6 General alarm Fan failure Internal communication fault Inverter thermal overload Inverter fault Inverter fuse blown Load short circuit Module 7 General alarm...
  • Page 100 7.4.4.3 Measurements table Description of the physical quantity I1 (I phase 1) mains 1 I2 (I phase 2) mains 1 I3 (I phase 3) mains 1 I1 (I phase 1) mains 2 I2 (I phase 2) mains 2 I3 (I phase 3) mains 2 I1 (I phase 1) output I2 (I phase 2) output I3 (I phase 3) output...
  • Page 101 Description of the physical quantity U mains 1 (phase 1) U mains 1 (phase 2) U mains 1 (phase 3) Nominal voltage of battery element ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Word (hex) Unit 34003991EN/DA Page 101/120...
  • Page 102: Sensor Data

    7.4.5 Sensor data 7.4.5.1 Status table Status description Input 1 alarm Input 2 alarm Alarm : humidity too low Alarm : humidity too high Alarm : temperature too low Alarm : temperature too high Communication fault Input 1 Input 2 ENERGIZE YOUR ENTERPRISE Network Management Card –...
  • Page 103 7.4.5.2 Measurements table Description of the physical quantity Temperature measure Maximum temperature Maximum temperature date (MSB) in Unix timestamp Maximum temperature date (LSB) in Unix timestamp Minimum temperature (° C) Minimum temperature date (MSB) in Unix timestamp Minimum temperature date (LSB) in Unix timestamp Humidity measure (%) Maximum humidity (%) Maximum humidity date (MSB) in Unix timestamp...
  • Page 104 7.4.5.3 Read of the personalization table Description High threshold temperature (° C) Low threshold temperature (° C) Temperature hysteresis (° C) Offset temperature High threshold humidity (%) Low threshold humidity (%) Humidity hysteresis (%) Humidity offset Inputs call mask – input 1 close notification Inputs call mask –...
  • Page 105: Other Data

    7.4.6 Other data Information description Manufacturer name Product name UPS model Serial number ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Word (hex) Example « MGE Office Protection Systems » « Pulsar » « 700 » « AN2E49008 » 34003991EN/DA Page 105/120...
  • Page 106: Appendices

    8 Appendices 8.1 Tables of alarms and events 8.1.1 Table of alarms List of time dated alarms Alarm on Battery fuse blown No Battery Battery temperature fault Battery charger fault Battery fault MAX charger voltage fault MIN charger voltage fault Charger temperature fault Rectifier fault Chopper fault...
  • Page 107 Inverter overload Inverter over temperature Inverter short circuit Inverter thermal overload Load not protected - On Automatic Bypass Load short circuit Load not powered Protection Lost Emergency button ON Fan fault Redundancy Lost Low battery UPS communication failed UPS data base not available UPS on battery UPS internal fault UPS overload...
  • Page 108 If the UPS is modular UPS, for each module: Battery fuse blown No Battery Battery temperature fault Battery charger fault Low battery Charger temperature fault MAX charger voltage fault MIN charger voltage fault Chopper fault Normal AC fuses blown Normal AC module fault Inverter fuses blown Inverter fault Inverter short circuit...
  • Page 109: Table Of Ups Events

    Positive DC bus too low Output switch (Q5N) open Normal AC NOK UPS on battery UPS overload UPS overtemperature Fan fault UPS communication failed 8.1.2 Table of UPS events List of time dated informations Alarm on Battery fuse blown Battery temperature fault No Battery Battery charger fault Charger temperature fault...
  • Page 110 Inverter fault Inverter overload Inverter overtemperature Inverter short circuit Inverter thermal overload Output switch (Q5N) open Load short circuit Single wave load fault Negative DC bus too high Positive DC bus too high Rectifier fault Negative DC bus too low Positive DC bus too low Protection Lost Redundancy Lost...
  • Page 111: Table Of System Alarms

    8.1.3 Table of system alarms Network Management Card startup Send test mail SUCCESS Send test mail ERROR Send mail to <recipient> ERROR <Sensor name> Communication failure <Sensor name> Communication restored Firmware upgraded Connected NSM list Full, last connection refused sendTrap()-> Unable to resolve hostname <hostname> SNMP Send Trap # <num>...
  • Page 112: Snmp Objects

    8.2 SNMP objects 8.2.1 MGE MIB The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed. The entire MIB description is available on Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705.1. MIB object SNMP Format upsmgIdentFamilyName String upsmgIdentModelName...
  • Page 113 mgoutputFrequency_1 deciHz mgoutputFrequency_2 deciHz mgoutputFrequency_3 deciHz mgoutputLoadPerPhase_1 mgoutputLoadPerPhase_2 mgoutputLoadPerPhase_3 mgoutputCurrent_1 deciAmps mgoutputCurrent_2 deciAmps mgoutputCurrent_3 deciAmps upsmgOutputOnBattery 1(yes) 2(no) upsmgOutputOnByPass 1(yes) 2(no) upsmgOutputUtilityOff 1(yes) 2(no) upsmgOutputInverterOff 1(yes) 2(no) upsmgOutputOverLoad 1(yes) 2(no) upsmgOutputOverTemp 1(yes) 2(no) upsmgAgentIpAddress upsmgAgentSubnetMask upsmgAgentDefGateway upsmgAgentType upsmgAgentMibVersion upsmgAgentFirmwareVersion upsmgAgentCommUPS 1(yes) 2(no) ENERGIZE YOUR ENTERPRISE Network Management Card...
  • Page 114 If the Environment Sensor is detected , the following information are managed. upsmgEnvironAmbientTemp 0.1 degré upsmgEnvironAmbientHumidity 0.1 % upsmgEnvironmentNum upsmgEnvironmentIndex upsmgEnvironmentComFailure 1(yes) 2(no) upsmgEnvironmentTemperature 0.1 degré upsmgEnvironmentTemperatureLo 1(yes) 2(no) upsmgEnvironmentTemperatureHi 1(yes) 2(no) upsmgEnvironmentHumidity 0.1 % upsmgEnvironmentHumidityLow 1(yes) 2(no) upsmgEnvironmentHumidityHigh 1(yes) 2(no) upsmgEnvironmentInput1State closed(1), open(2) upsmgEnvironmentInput2State...
  • Page 115: Table Des Traps : (1.3.6.1.4.1.705.1.11)

    8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11) SNMP traps are sent when alarms appears and desappears. Level : 1:informational , 2:major, 3:critical MIB TRAP -upsmgBatteryFault -upsmgBatteryOK -upsmgAtLowBattery -upsmgFromLowBattery -upsmgChargerFault -upsmgChargerOK -upsmgOnBattery -upsmgReturnFromBattery -upsmgOnByPass -upsmgReturnFromByPass -upsmgUtilityFailure -upsmgUtilityRestored -upsmgOverLoad -upsmgLoadOK -upsmgOverTemperature -upsmgTemperatureOK -upsmgOffToStart -upsmgOffInProgress -upsmgCommunicationFailure -upsmgCommunicationRestored...
  • Page 116 - upsEnvironmentInput1Open - upsEnvironmentInput2Open - upsEnvironmentInput2Closed The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual Trap 62 Level 2 Trap 64 Level 2 Trap 63...
  • Page 117: Glossary

    9 Glossary Bootp: Protocol based on UDP used to allocate an IP address corresponding to an Ethernet card during the startup phase. Defined by the RCF 951 Community name: Access key to access SNMP agent information DHCP Dynamic Host Configuration Protocol This IETF protocol enables remote, automatic, self-configuration of the IP addresses of a workstation.
  • Page 118 ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 118/120...
  • Page 119 NMS NETWORK MANAGEMENT STATION (SNMP) The dedicated PC or workstation is used on the company’s networks to administrate all devices connected to the network. Data are transmitted using the SNMP protocol. Popular NMS systems include HP OpenView, IBM Tivoli, CA Unicenter, etc.
  • Page 120 programmed to perform specific tasks upon reception of the traps. ENERGIZE YOUR ENTERPRISE Network Management Card – User Manual 34003991EN/DA Page 120/120...

This manual is also suitable for:

66103

Table of Contents