Wiring - IDTECK iCON100 Quick Installation Manual

Single door access control panel
Hide thumbs Also See for iCON100:
Table of Contents

Advertisement

Quick Installation Guide

7. Wiring

7.1 Power
Connect (+) wire of DC 12V power to +12V terminal
Connect GND (-) wire of DC 12V power to GND terminal
7.2 Input Connections
 Exit Button Connection (Input #1)
- Connect one wire from an Exit Button to Input #1
- Connect the other wire from the Exit Button to the GND
 Door Contact Sensor Connection (Input #2)
- Connect one wire from a Door Contact Sensor to Input #2
- Connect the other wire from the Door Contact Sensor to GND
 Auxiliary Input Connection (Applied to Input #3, Input #4 and Input #5)
- Connect one wire from an Auxiliary Input Device to one of the Input #3, #4 and #5.
- Connect the other wire from the Auxiliary Input Device to GND
Figure: Input Devices Connection
 2.2K Resistance Connection for 'Cut Off Check'
To use the 'Cut Off Check' function, you have to connect 2.2K resistance between Input wire (ex. Orange) and GND.
Firstly you choose to use 'Cut Off Check'. Follow the process as [F2 SETUP MENU] ->"5. IN/OUT DEFINE" 
"21.CUT OFF CHECK". For setting of output, follow the process as [F2 SETUP MENU]->"5. IN/OUT DEFINE"  "18.
CUT OFF ALARM".
Figure: 2.2K Resistance Connection for 'Cut Off Check'