7.2.6

Technical data

In general, the details in section 1 "System data and system structure" of volume 2 of the system description "Advant
Controller 31" apply as technical data. Supplementary and deviating data is listed below.
7.2.6.1
General data
Number of serial interfaces
Number of parallel interfaces
Built-in application software memory
Diagnosis
Operating and error displays
Conductor cross section for the
removable terminals
7.2.6.2
Supply voltage for 07 MK 92 R1161
Rated supply voltage
Power dissipation
Max. current consumption
with rated voltage
with supply voltage 30 V
Protection against reversed terminal connection
7.2.6.3
Connection of serial interfaces COM3, COM4
Interface standard
Programming with 907 MK 92
Man-machine communication
Electrical isolation
Potential differences
Terminal assignment and
description of the interfaces COM3, COM4
7.2.6.4
Connection of serial interfaces COM5, COM6
Interface standard
Man-machine communication
Electrical isolation
Potential differences
Terminal assignment and
description of the interfaces COM5, COM6
Advant Controller 31 / Issued: 10.99
Hardware
7.2-13
4
1 networking interface for connecting to the
Advant Controller 31 basic unit
Flash EPROM 128 kbytes
4 configurable LEDs: LED1...4
(controlled by the application program)
3 LEDs: RUN, ERR, Supply
max. 2.5 mm
2
24 V DC
typ. 2.5 W
210 mA
170 mA
yes (only when units with electrically isolated interfaces
are connected to COM5/COM6)
EIA RS-232 or EIA RS-422 or EIA RS-485
via IBM-PC (or compatible)
yes, e.g. with an operating station
yes, interfaces with respect to each other and with
respect to the rest of the unit (also see Figure 7.2-5)
So that no earthing potential differences arise between
the 07 MK 92 and the peripheral units connected to
COM3 and COM4, the latter are supplied from the
switch-gear cabinet mains socket (also see earthing
connections in Figure 7.2-5).
see page 7.2-7 onwards
EIA RS-232
yes, e.g. with an operating station
none
see COM3, COM4
see page 7.2-9 onwards