ABB 07 MK 92 R1161 Operating Manual

Intelligent decentralized automation system communication module advant controller 31

Advertisement

Quick Links

Operating Manual
Hardware
COM4
COM3
ABB STOTZ-KONTAKT
RUN
LED
1
2
3
4
RUN
ERR
Supply
Advant Controller 31
Intelligent Decentralized
Automation System
Communication module
07 MK 92 R1161
07 MK 92
Advant Controller 31
Serial Communication Processor

Advertisement

Table of Contents
loading

Summary of Contents for ABB 07 MK 92 R1161

  • Page 1 Operating Manual Advant Controller 31 Hardware Intelligent Decentralized Automation System Communication module 07 MK 92 R1161 COM4 07 MK 92 Advant Controller 31 Serial Communication Processor COM3 Supply ABB STOTZ-KONTAKT...
  • Page 3: Table Of Contents

    Fig. 7.2-1: Communication module 07 MK 92 R1161 Contents 7.2.1 Brief description 7.2.1 Brief description........7.2-1 The 07 MK 92 R1161 communication module is a freely 7.2.2 Structure of the front panel elements ..7.2-3 programmable interface module with 4 serial interfaces. 7.2.3 Electrical connection ......7.2-4 The communication module allows external units to be 7.2.3.1...
  • Page 4 Programming is in the standard language ”C”. The exchange of data between the serial communication module and the AC31 basic unit is realized by function blocks in the basic unit. 07 MK 92 R1161 7.2-2 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 5: Structure Of The Front Panel Elements

    Advant Controller 31 Serial Comm. Processor Supp. Fig. 7.2-2: Communication module 07 MK 92 R1161 with reference points (see below for explanation) 1 Mounting the unit on a DIN rail The status of the application program is indicated by the...
  • Page 6: Electrical Connection

    Looping through the supply voltage (24 V DC) from · the 07 KT 97 to the 07 MK 92 Earthing the switch-gear cabinet mains socket · Handling serial interfaces · 07 MK 92 R1161 7.2-4 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 7 Communication module 07 MK 92 at basic unit 07 KT 97 (Section 7.2.3 Electrical connection applies in the same way to 07 KR 91, 07 KT 92 to 07 KT 97.) Hardware 7.2-5 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 8: Connecting The Supply Voltage

    24 V DC-IN supply voltage 6 mm PGND cross section COM6 DC-IN Connect to the Faston of the basic unit (see Figure 7.2-6) Fig. 7.2-5: Electrical isolation and notes on earthing 07 MK 92 R1161 7.2-6 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 9 Use supplied connection parts L+ / +24 V DC M / 0 V Switch-gear cabinet earth Fig. 7.2-6: Earthing connections and voltage supply for 07 MK 92 Hardware 7.2-7 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 10: Serial Interfaces

    Both interfaces are electrically isolated. (XON/XOFF) Connection Automatic processing of the HW handshake · (RTS/CTS) Connection is via a 15-pole D-SUB connector (female). Error detection · (parity, framing, overrun, break) 07 MK 92 R1161 7.2-8 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 11 This mode is not used with COM4. (Pin 6 open) Application mode Pin 6 jumpered in the interface connector with pin 7 (0V SGND) Fig. 7.2-8: Terminal assignment for the serial interface COM4 Hardware 7.2-9 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 12 14 SGND Signal Ground (0V) 28 SGND Signal Ground (0V) Fig. 7.2-9: Terminal assignment of the Fig. 7.2-10: Terminal assignment of the serial interface COM5 serial interface COM6 07 MK 92 R1161 7.2-10 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 13: Networking Interface

    3. Place both units on a level surface and slide them to- gether so that they engage. 4. Slide in the connection part to fix the housing in posi- tion. Hardware 7.2-11 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 14: Diagnosis

    IBM-compatible PC. The PC is con- cation module 07 MK 92 and configuration examples. nected with the COM3 interface of the communication module. 07 MK 92 R1161 7.2-12 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 15: Technical Data

    Operating and error displays 3 LEDs: RUN, ERR, Supply Conductor cross section for the max. 2.5 mm removable terminals 7.2.6.2 Supply voltage for 07 MK 92 R1161 Rated supply voltage 24 V DC Power dissipation typ. 2.5 W Max. current consumption...
  • Page 16 Mounting position vertical, terminals above and below Cooling The natural convection cooling must not be hindered by cable ducts or other material mounted in the switch- gear cabinet. 07 MK 92 R1161 7.2-14 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 17 Programming and test software 907 MK 92 Order No. GJP5 2074 00 R0102 907 MK 92 consists of: – Documentation – Software – Basic functions for 07 MK 92 R1161 – Paradigm Locate V 3.21 Hardware 7.2-15 Hardware 07 MK 92 R1161...
  • Page 18: System Cables

    Transmit Data Data Terminal Ready Receive Data Carrier Detect Request To Send SGND Signal Ground Clear To Send Fig. 7.2-17: Connecting COM3 to PC (9-pole) as EIA RS-232 07 MK 92 R1161 7.2-16 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 19 COM3, COM4 as EIA RS-485 interface 15-pole, male 07 MK 92 Shield PGND PROG SGND RxD–P, TxD–P Bus–P RxD–N, TxD–N Bus–N Fig. 7.2-20: COM3, COM4 as EIA RS-485 interface Hardware 7.2-17 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 20 Fig. 7.2-21: COM5 as EIA RS-232 interface 7.2.7.7 COM6 as EIA RS-232 interface Signal Terminals 07 MK 92 Shield PGND SGND SGND Fig. 7.2-22: COM6 as EIA RS-232 interface 07 MK 92 R1161 7.2-18 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 21: Memory Areas In 07 Mk 92

    RS-485 change-over COM3 Port P1LTCH Bit 3 Control of RTS COM4 Port P1LTCH Bit 6 RS-485 change-over COM4 The addresses of the ports are listed in the file MK92HW.H Hardware 7.2-19 Hardware 07 MK 92 R1161 Advant Controller 31 / Issued: 10.99...
  • Page 22 07 MK 92 R1161 7.2-20 Hardware Advant Controller 31 / Issued: 10.99...
  • Page 24 ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 82 Postfach 101680 D-69123 Heidelberg D-69006 Heidelberg Telephone +49 6221 701-0 Telefax +49 6221 701-1111 E-Mail desst.helpline@de.abb.com Internet http://www.abb.de/sst...