Programming Information for Control FPWIN Pro
ErrEvent
Explanation
50
Length in COS or cyclic device
response unequal to produced
connection size.
51
UCMM group not supported.
52
Device keying failed: vendor ID
mismatch.
53
Device keying failed: device type
mismatch.
54
Device keying failed: product code
mismatch.
55
Device keying failed: revision
mismatch.
59
Double device address configured in
current configuration.
60
Whole size indicator of one device
data set is corrupt.
61
Size of the additional table for
predefined master-slave connections
is corrupt.
62
Size of predefined master-slave I/O
configuration table is corrupt.
63
Predefined master-slave I/O
configuration does not correspond to
the additional table.
64
Size indicator of parameter data table
is corrupt.
65
Number of inputs declared in the
additional table does not correspond
to the number in the I/O configuration
table.
66
Number of outputs declared in the
additional table does not correspond
to the number in the I/O configuration
table.
67
Unknown data type in I/O
configuration detected.
68
Data type of a defined I/O unit in a
connection does not correspond with
the defined data size.
69
Output address configured for one unit
exceeds the possible address range of
3584 bytes.
44
Source of error
Device
Device
Device/configuration
Device/configuration
Device/configuration
Device/configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
FMU Technical Manual
Recommendation
Change the UCMM group.
Check vendor ID configured with
device's vendor ID.
Check device type configured
with device's device type.
Check product code configured
with device's product code.
Check revision configured with
device's revision.
Each device in DeviceNet must
have its own MAC ID.
Download error in the current
database. Contact technical
support.
Download error in the current
database. Contact technical
support.
Download error in the current
database. Contact technical
support.
Number of I/O units and the
number of configured offset
addresses are different.
Value of size indicator too small.
Each entry in the I/O
configuration must have only one
entry in the additional table.
Each entry in the I/O
configuration must have only one
entry in the additional table.
Data types supported:
BOOL, BYTE, WORD, DWORD
and STRING only.
The following types and size are
valid:
• BOOLEAN = 1 byte
• Unit 8 = 1 byte
• Unit 16 = 2 bytes
Unit 32 = 4 bytes
The process data image is
limited to 3584 bytes.