The following error numbers are valid for the error event if "Error remote address" is not equal to
255.
ErrEvent
Explanation
0
No errors.
1
Device guarding failed after device
was operational.
30
Device access timeout.
32
Device rejects access with unknown
error code.
35
Device response in allocation phase
with connection error.
36
Connection produced (process data
input length from the FMU's
point-of-view) is different from the one
configured.
37
Size of connection consumed
(process data output length from the
FMU's point-of-view) is different from
the one configured.
38
Device service response telegram
unknown and not handled.
39
Connection already requested.
40
Number of CAN message data bytes
read in the produced or consumed
connection size response unequal to
4.
41
Predefined master-slave connection
already exits.
42
Length in polling device response
unequal to produced connection size.
43
Sequence error in device polling
response.
44
Fragment error in device polling
response.
45
Sequence error in device polling
response.
46
Length in bit strobe device response
unequal to produced connection size.
47
Sequence error in device COS or
cyclic response.
48
Fragment error in device COS or
cyclic response.
49
Sequence error in device COS or
cyclic response.
Source of error
Device
Device
Device
Device
Device/configuration
Device/configuration
Device/configuration
Device
Device
Device/FMU
Device
Device
Device
Device
Device
Device
Device
Device
5.3 FMU_DataExchange
Recommendation
Check if device is still running.
Device does not respond. Check
the baud rate and MAC ID.
Use single-device diagnostic to
get reject code.
Use single-device diagnostic to
get additional reject code.
Use single-device diagnostic to
get true produced connection
size.
Use single-device diagnostic to
get true consumed connection
size.
Use single-device diagnostic to
get true consumed connection
size.
Connection will be automatically
released.
Device cannot operate with the
FMU and norm description.
Connection will be automatically
released.
Two initial segments in
multiplexed transfer were
received.
Fragmentation counter during
multiplexed transfer differs from
the one expected.
Middle or last segment was
received before the first
segment.
Two initial segments in
multiplexed transfer were
received.
Fragmentation counter during
multiplexed transfer differs from
the one expected.
Middle or last segment was
received before the first
segment.
43