Panasonic FMU Technical Manual page 38

Programmable logic controller
Table of Contents

Advertisement

FMU Technical Manual
2. Wrap the end of the cable with 38mm (1.5in.) of shrink wrap, covering part of
the exposed conductors and part of the trunk line insulation.
3. Strip 8.1mm (0.32in.) of the insulation from the end of each of the insulated
conductors.
4. Insert each conductor into the appropriate clamping cavity of the open style
connector or the screw terminal on the device, according to the color of the
cable insulation:
Wire color
White
Blue
Bare
Black
Red
5. Tighten the clamping screws to secure each conductor. The male contacts of
the device connector must match the female contacts of the connector.
NOTES
When removing the wire's insulation, be careful not to scratch the core wire.
Do not twist the wires to connect them.
Do not solder the wires to connect them. The solder may break due to
vibration.
Jacket
Jacket
Wire identity
CAN_H
CAN_L
Drain
V-
V+
4.4 Wiring of the FP-FMU Connectors
Shrink wrap
38mm
Shrink wrap
Usage
Signal
Signal
Shield
Power
Power
8.1mm