Honeywell 13270-01LB Data, Installation And Commissioning Manual page 18

Fire control and repeat panels, conventional 1, 2, 4 and 8 zone panel range
Hide thumbs Also See for 13270-01LB:
Table of Contents

Advertisement

Fire Panels
PSU Fault Indications
At Main Panel
Green Power Indicator
Steady
Slow Flash
Slow Flash
Slow Flash
* If Access/Function indicator flashes slowly, there is either a comms fault, an earth fault or a PSU fault on the Repeat Panel.
At Repeat Panel
Green Power Indicator
Steady
Steady
Steady
Steady
Slow Flash
Slow Flash
* If Access/Function indicator flashes slowly, there is a comms fault, between the Main Panel and the Repeat Panel.
NOTE: If there is a PSU fault at the Main Panel and the Repeat Panel, then priority is given to the fault at the
Main Panel
Earth Fault Indications
At Main panel
Fault -
Yellow
Earth fault
Steady
indications
NOTE: If a Repeat panel is connected, the ACCESS/FUNCTION lamp will pulse slowly as well.
At Repeat Panel
Earth Fault Indicator
4188-424 issue 4_Part 1_10-09
Power Fault Indicator
Off
Slow Flash
Fast Flash
Steady
Power Fault Indicator
Off
Slow Flash
Fast Flash
Steady
Slow Flash
Fast Flash
Earth -
Power -
Buzzer
Yellow
Green
Pulse
On
Pulse
Slowly
Slowly
Off
Steady Indication
Meaning
No PSU Faults
Mains failed (Common Fault indicator also flashes to save batteries*)
Battery disconnected/Battery fault or Charger fault
Auxiliary supply/sounder output supply fault
Meaning
No PSU Fault in either Main Panel or Repeat panel
Mains failed at Main Panel
Battery disconnected/Battery fault/Charger fault at Main Panel
Auxiliary supply/sounder output supply fault at Main Panel
Mains failed at Repeat Panel
Battery disconnected/Battery fault/Charger fault at Repeat Panel
Auxiliary relay contacts
normally de-energised
Normal
No earth fault at the Repeat Panel or the Main Panel
Earth fault local to the Main Panel
18
Fault finding
Common fault -
Common fire -
normally active
normally deactive
Deactive
Deactive