The energy needed for operation is not sup-
plied directly by the auxiliary power supply, but
is always "stored" in the capacitor which acts
as an energy accumulator, and therefore op-
eration always takes place with constant speeds
and times, regardless of the divergence of the
power supply voltage from the rated value.
The auxiliary power supply only has the aim of
keeping the capacitor charged. Consumption
is therefore minimal. The power required is less
than 5 W. In order to re-instate the rated en-
ergy value in the capacitor following an opera-
tion, there is an inrush of 15 W for a duration of
a few tens of milliseconds.
Careful selection of the components and a pre-
cise design make the electronic multi-voltage
1.3. Characteristics
Contactor
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated service current
Short-time withstand current
Short-time withstand current for 1 s
Short-time withstand current for 30 s
Rated peak current
Rated short-circuit time (tk)
Rated values
Operations / hour
Rated load and overload characteristics in category of use:
- (Category AC4) 100 closing operations
- (Category AC4) 25 opening operations
Rated voltage of the switching devices and auxiliary circuits
Feeder type 1 (24 ... 60 DC)
Feeder type 2 (110 ... 130 AC-DC)
Feeder type 3 (220 ... 250 AC-DC)
Normal current
Electrical life (category AC3)
Electrical life at rated current (cat. AC1 - electrical latching)
Mechanical life
Short-circuit breaking capacity (O-3min-CO-3min-CO)
Short-circuit making capacity (O-3min-CO-3min-CO)
Opening time with electrical latching
Closing time
Weight
Overall dimensions
Tropicalisation
(*) Without fuses.
feeder extremely reliable, unaffected by elec-
tromagnetic interference generated by the sur-
rounding environment and free of any emis-
sions which may affect other apparatus placed
in the vicinity.
These characteristics have made it possible for
the V-Contact VSC contactors to pass the elec-
tromagnetic compatibility tests (EMC) and ob-
tain the CE mark.

1.2. Versions available

The V-Contact VSC are available in the fixed
and withdrawable version with rated voltages
of 7.2 kV and 12 kV.
Their main characteristics are listed below.
Reference
IEC 60470
[kV]
4.1
[kV]
[kVbil]
[Hz]
[A]
4.101
[A]
4.5
[A]
4.5
[kA]
4.6
[s]
4.7
[N.]
[kA]
4.103, 4.104
[kA]
4.103, 4.104
4.8, 4.9
[A]
4.4.101
[N.]
29.mar
[N.]
29.mar
[N.]
[A]
4.107, 6.104
[A]
4.107, 6.104
[ms]
[ms]
[Kg]
[mm] H
[mm] W
[mm] D
721-2-1
VSC 7
VSC 12
VSC/P 7
7.2
12
7.2
23
28
23
60
75
60
50-60
50-60
50-60
400
400
400
6.000
4.000
6.000
2.500
2.500
2.500
15
15
15
1
1
1
900
900
900
4.000
4.000
4.000
4.000
4.000
4.000
400
400
400
100.000
100.000
100.000
1.000.000
1.000.000
1.000.000
1.000.000
1.000.000
1.000.000
6.000
4.000
6.000
15.000
8.000
15.000
20..30
20..30
20...30
30..50
30..50
30...50
20
20
49(*)
371
391
635
350
350
531
215
215
657
VSC/P 12
12
28
75
50-60
400
4.000
2.500
15
1
900
4.000
4.000
400
100.000
1.000.000
1.000.000
4.000
8.000
20...30
30...50
49(*)
635
531
657
7